| Date |
Text |
| 2008-11-04 13:47:29 | |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PER PREVIOUS REVIEW NOTES. PLEASE KNOW THE |
| | MINIMUM LOCATIONS, LEVELS AND HEIGHTS FOR HORNS, |
| | STROBES, HORN/STROBE PULL STATIONS ARE TO BE SHOWN ON |
| | PLANS AS A BASE DESIGNER PER FS 633. |
| | THE PLANS STATE THE SCOPE OF WORK IS UNDER SEPARATE |
| | PERMIT AND STATES THE CODE SHALL BE MET. MAY NOT QUOTE |
| | THE CODE IN LIEU OF SPECIFIC DETAIL. |
| | FBC 11-4.28.1,.2. AND .3. |
| | |
| | 2) NOTE: PLEASE BE SURE THE ARCHITECTURAL PLANS ARE |
| | REVISED WITH ELECTRICAL REFLECTED PLANS. |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | FBC 13-415.1.ABC.1.1, .1.2 |
| | |
| | 3) NOTE: PLEASE SEE THE TIME CURVE COORDINATION STUDY |
| | SUBMITTED IS NOT SIGNED DATED OR SEALED FOR REVIEW. ALL |
| | DOCUMENTS MUST HAVE COMPLETED TITLE BLOCKS, SIGNED, |
| | DATED AND SEALED PER FAC61G15-23.002, FS 471.025 |
| | |
| | 4) NOTE: PLEASE SEE SECTION OF CODE SHOULD HAVE BEEN |
| | NEC 517 PART II. THIS WAS TYPED PREVIOUSLY AS 11 IN |
| | ERROR BY REVIEWER. PLEASE ADJUST. IF THIS WERE THE ONLY |
| | COMMENT THIS COULD HAVE BEEN REDLINED. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |