Plan Review Notes
Plan Review Notes For Permit 08080547
Permit Number 08080547
Review Stop P
Sequence Number 1
Notes
Date Text
2008-09-02 09:52:36DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REVISIONS
 NFPA 99 1999
  
 1. SHT A-1 CODE INFORMATION TO INCLUDE FBC W/2007
 REVISIONS ADDED TO OTHER REVISIONS INDICATED & NFPA 99
 TO BE 1999 EDITION PER FBC-2004 PLUMBING CHAPTER 13.
  
 2. SHT P1.01 APPLICABLE CODES & STANDARDS. NFPA 99 TO
 BE 1999 EDITION PER FBC-2004 PLUMBING CHAPTER 13 &
 FBC-2004 SHALL INCLUDE 2007 REVISIONS ALSO.
  
 ****INFORMATIONAL****
 ALTHOUGH THE MEDGAS IS REVIEWED UNDER NFPA 99 1999
 EDITION, AHCA (AGENCY FOR HEALTH CARE ADMINISTRATORS)
 WILL BE INSPECTING UNDER NFPA 99 2005 EDITION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  