| 2008-09-15 09:26:02 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE PLANS STATE THE FIRE ALARM |
| | SYSTEM SHALL COMPLY WITH NFPA-72. HOWEVER BASED ON MANY |
| | ASPECTS OF THE FLORIDA BUILDING CODE IN CHAPTER 11 |
| | THERE ARE ITEMS WHICH ARE SUBSTANTIALLY MORE |
| | RESTRICTIVE. PLEASE SEE FBC 11-4.28,.1,.2 AND .3. |
| | PLEASE BE SURE TO STATE ALL MINIMUM LEVELS FOR ADA |
| | COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2.ABC.1.1, .1.2. |
| | |
| | 3) NOTE: PLEASE INCLUDE LIGHTING CONTROLS FOR NEW WORK |
| | BEING INSTALLED PER 13-415.1.ABC.1.1, .1.2. |
| | |
| | 4) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE |
| | REVISED ON PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 1999 NFPA-99 |
| | |
| | 5) NOTE: PLEASE INCLUDE NOTES ON PLANS FOR NEC 517 PART |
| | 11. MAY STATE ONLY THE SECTION. |
| | |
| | 6) NOTE: PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND |
| | SO THAT COMPLIANCE WITH FBC CHAPTER 13 AS NOTED ABOVE |
| | CAN BE VERIFIED. |
| | |
| | 7) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION |
| | STUDY FOR NEW PANEL BACK TO MAIN. |
| | 240.12, NFPA-99 |
| | PLEASE ALSO PROVIDE SELECTIVE COORDINATION OF GFCI PER |
| | 517.17, 3-3.2.1.5 |
| | |
| | ** NOTES ON PLANS MENTIONS CONTRACTOR TO PROVIDE |
| | HOWEVER THIS NEEDS TO BE PART OF THE SUBMITTED PLANS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH |
| | INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK |
| | WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE |
| | REVIEW. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |