Plan Review Notes
Plan Review Notes For Permit 08080515
Permit Number 08080515
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-26 10:33:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 2)A/C SYSTEM MODEL NUMBER A.H.U. FSM2X30 WITH C.U.
 N2A330AKB LISTED ON THE A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1. (AIR HANDLER
 NOT MATCHED WITH THIS CONDENSER UNIT).
  
 3) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY, PER 2004 F.B.C. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]