Plan Review Notes
Plan Review Notes For Permit 08080507
Permit Number 08080507
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-27 12:00:06PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE (FBC-2004 WITH 2007
 REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED
 BELOW.
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS
 F-1 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2,
 AND I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP
 U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 NOTE: PLANS APPREAR TO BE A BUSSINESS, GROUP B. PLEASE
 KNOW THAT PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES FOR A BUSSINESS
 ARE AS FOLLOWS.
  
 WATER CLOSETS= 1 PER 25 FOR THE FIRST 50 AND 1 PER 50
 FOR THE REMAINDER EXCEEDING 50.
  
 LAVATORIES= 1 PER 40 FOR THE FIRST 50 AND 1 PER 80 FOR
 THE REMAINDER EXCEEDING 50.
  
 DRINKING FOUNTAIN= 1 PER 100.
  
 THE SUBMITTED PLANS ARE NOT INDICATING A DRINKING
 FOUNTAIN. PLEASE KNOW THAT ONE IS REQUIRED AND THAT IT
 SHALL BE ACCESSIBLE PER THE FBC-2004 CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
  
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
  
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
  
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
  
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 4. SHEET A-1 FLOOR PLAN TOILET 1, ROOM #103 AND TOILET
 2, ROOM # 104: PLEASE KNOW THAT THE DOOR CAN NOT SWING
 INTO THE CLEAR FLOOR SPACE OF THE ACCESSIBLE LAVATORIES
 (LAVATORY CLEAR FLOOR SPACE IS 30" X 48" & MAX. 19"
 UNDER LAV.). PER FBC-2004, CHAPTER 11, FLORIDA
 ACCESSIBILTY CODE SECTION 11-4.22.2.
  
 5. SHEET A-3 DETAIL 4: CORRELATE THE DETAIL WITH THE
 BREAKROOM REFERENCE NOTES AND DELETE THE CABINET DOORS
 AND BASE AT THE ACCESSIBLE SINK LOCATION. CLEARLY
 INDICATE AN OPEN FRONT ON THE DETAIL AT THE ACCESSIBLE
 SINK LOCATION. PER FBC-2004, CHAPTER 11, FLORDA
 ACCESSIBLITY CODE SECTION 11-4.24.5 CLEAR FLOOR SPACE.
 NOTE: CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR THE
 ACCESSIBLE SINK ON SHEET A-1 FLOOR PLAN. PER SECTION
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
  
 6. SHEET P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN
 ARE INDICATING A HORIZONTAL DRY VENT FOR THE WATER
 CLOSETS. HORIZONTAL DRY VENTS ARE UNACCEPTABLE PER THE
 FBC-2004 PLUMBING SECTION 905.3 VENT CONNECTIONS TO
 DRAINAGE SYSTEM.
  
 7. SHEET P-1 RESTROOMS DETAIL AND FLOOR PLAN: TOILET
 1, ROOM #103 AND TOILET 2, ROOM # 104: PLEASE KNOW THAT
 THE DOOR CAN NOT SWING INTO THE CLEAR FLOOR SPACE OF
 THE ACCESSIBLE LAVATORIES (LAVATORY CLEAR FLOOR SPACE
 IS 30" X 48" & MAX. 19" UNDER LAV.). PER FBC-2004,
 CHAPTER 11, FLORIDA ACCESSIBILTY CODE SECTION
 11-4.22.2.
  
 8. SHEET P-1 RESTROOMS DETAIL PLAN: PLEASE
 CLARIFY/CORRECT THE FOLLOWING PER THE FBC-2004 CHAPTER
 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 A} CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR THE
 WATER CLOSET IN THE DETAIL (60" X 48"). PER SECTION
 11-4.16.2 CLEAR FLOOR SPACE.
  
 B} CLEARLY INDICATE THAT THE FLUSH CONTROLS FOR THE
 WATER CLOSETS SHALL BE MOUNTED ON THE WIDE SIDE OF
 FIXTURE MAXIMUM OF 44" HIGH. PER SECTION 11-4.16.5
 FLUSH CONTROLS.
  
 C} CLEARLY INDICATE THE LAVATORIES CLEAR FLOOR SPACE
 IN THE DETAIL (30" X 48" AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE LAVATORIES). PER SECTION 11-4.19.3
 CLEAR FLOOR SPACE.
  
 D} RESTROOM REFERENCE NOTES (C): NOTE C, STATES "THEN
 9" TO WALL", PLEASE CLARIFY THIS AS BEING THE TOE
 CLEARANCE AND THAT IT IS 9" MIN UP FROM FINNISH FLOOR
 AND 6" MAX FROM WALL. PER SECTION 11-4.19.2 HEIGHT AND
 CLEARANCES, FIGURE 31 LAVATORY CLEARANCES DETAIL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  