| 2008-09-03 11:45:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) THE MECHANICAL CONTRACTOR NEEDS TO APPLY FOR THE |
| | MECHANICAL PERMIT BEFORE PASSING PLAN REVIEW TO COMPLY |
| | WITH, FAC 61G4-12.016 EXEMPTION; PRACTICE OF |
| | ENGINEERING. |
| | A CONTRACTOR LICENSED UNDER CHAPTER 489, PART I, F.S., |
| | IS EXEMPTED FROM LICENSURE AS AN ENGINEER PURSUANT TO |
| | THE TERMS OF SECTION 471.003(2)(I), F.S., "ONLY WHEN HE |
| | INSTALLS THE SYSTEM HE DESIGNS". VIOLATION OF THIS RULE |
| | WILL BE CONSIDERED A VIOLATION OF SECTION |
| | 489.129(1)(M), F.S. |
| | |
| | 2) PLAN M-1 OUTSIDE AIR SCHEDULE DOES NOT COMPLY WITH |
| | ASHRAE 62.1-2004 TABLE 6-1, OR WITH 2004 FBC/M TABLE |
| | 403.3. PLEASE STATE WHERE THE CALCULATIONS ARE COMING |
| | FROM AND CORRECT. SEE 2004 FBC/M 403.3 AND 403.4. |
| | |
| | 3) SHOW ON MECHANICAL PLAN M-1 THE OUTSIDE AIR DUCTS, |
| | PER 2004 FBC/M 401. |
| | |
| | 4) PLEASE SHOW EXISTING A/C SYSTEM #1 INFORMATION IN |
| | THE EQUIPMENT SCHEDULE (MAKE, MODEL NUMBERS, CFM'S, |
| | TOTAL BTU'S AND HEATER SIZE) SO A COMPLETE REVIEW CAN |
| | BE DONE (LIST AS EXISTING), PER 2004 FBC |
| | 13-407.1.ABC.1.1. |
| | |
| | 5) THE MECHANICAL PLAN SHOWS A SUPPLY AIR GRILL AS S-3 |
| | AND A RETURN AIR GRILL AS R-4, THE AIR DISTRIBUTION |
| | SCHEDULE ON THE PLAN DOES NOT LISTS THEM. PLEASE |
| | CORRECT. |
| | |