Plan Review Notes
Plan Review Notes For Permit 08080507
Permit Number 08080507
Review Stop M
Sequence Number 1
Notes
Date Text
2008-09-03 11:45:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MECHANICAL CONTRACTOR NEEDS TO APPLY FOR THE
 MECHANICAL PERMIT BEFORE PASSING PLAN REVIEW TO COMPLY
 WITH, FAC 61G4-12.016 EXEMPTION; PRACTICE OF
 ENGINEERING.
 A CONTRACTOR LICENSED UNDER CHAPTER 489, PART I, F.S.,
 IS EXEMPTED FROM LICENSURE AS AN ENGINEER PURSUANT TO
 THE TERMS OF SECTION 471.003(2)(I), F.S., "ONLY WHEN HE
 INSTALLS THE SYSTEM HE DESIGNS". VIOLATION OF THIS RULE
 WILL BE CONSIDERED A VIOLATION OF SECTION
 489.129(1)(M), F.S.
  
 2) PLAN M-1 OUTSIDE AIR SCHEDULE DOES NOT COMPLY WITH
 ASHRAE 62.1-2004 TABLE 6-1, OR WITH 2004 FBC/M TABLE
 403.3. PLEASE STATE WHERE THE CALCULATIONS ARE COMING
 FROM AND CORRECT. SEE 2004 FBC/M 403.3 AND 403.4.
  
 3) SHOW ON MECHANICAL PLAN M-1 THE OUTSIDE AIR DUCTS,
 PER 2004 FBC/M 401.
  
 4) PLEASE SHOW EXISTING A/C SYSTEM #1 INFORMATION IN
 THE EQUIPMENT SCHEDULE (MAKE, MODEL NUMBERS, CFM'S,
 TOTAL BTU'S AND HEATER SIZE) SO A COMPLETE REVIEW CAN
 BE DONE (LIST AS EXISTING), PER 2004 FBC
 13-407.1.ABC.1.1.
  
 5) THE MECHANICAL PLAN SHOWS A SUPPLY AIR GRILL AS S-3
 AND A RETURN AIR GRILL AS R-4, THE AIR DISTRIBUTION
 SCHEDULE ON THE PLAN DOES NOT LISTS THEM. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]