| 2008-09-02 14:43:45 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} ON SHEET E-1 THERE ARE TWO PANELS LOCATED ON THE |
| | PLAN BUT ONLY A SCHEDULE FOR PANEL "B". PANEL "B" IS |
| | RATED AT 225 AMPS MLO WITH #2/0 FEEDERS, INDICATE THE |
| | OCP FOR THE FEEDERS 215.5 NEC. |
| | |
| | 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | NEW DEVICES AND EQUIPMENT (WATER HEATER) 106.3.5 FBC. |
| | |
| | 3} PER 700.12(F)(4) "HE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES." INDICATE COMPLIANCE ON |
| | THE PLAN SHEET E-2 |
| | |
| | 4} PER 13-415.2.ABC.1.1. PAGE #2 OF THE ENERGY GAUGE |
| | INPUT DATA REPORT, DOES NOT INDICATE THE CORRECT NUMBER |
| | OF FIXTURES AS SHOWN ON THE PLAN, ALL THAT IS REQUIRED |
| | FOR THE ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE |
| | REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE |
| | CALCULATION PROCEDURES, GENERAL. THAT REQUIREMENT IS |
| | COMPLIANT ON SHEET E-2, THEREFORE FORM 400A WILL NOT BE |
| | REVIEWED FOR THE ELECTRICAL COMPLIANCE OF CHAPTER 13 |
| | FBC. |
| | |
| | PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR |
| | REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE |
| | REMOVED FOR DEMOLITION. |
| | |
| | PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD |
| | SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO THE |
| | COMMENTS MADE IN THIS REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |