| Date |
Text |
| 2008-09-04 16:36:10 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. THE EXHAUST FAN ON THE ROOF APPEARS TO BE WITHIN 10 |
| | FEET OF THE ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE |
| | FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE |
| | LOCATED WITHIN 10 FEET OF A ROOF EDGE IN ACCORDANCE |
| | WITH FBCM 304.10. THE GUARD SHALL EXTEND NOT LESS THAN |
| | 30 INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, |
| | FAN OR COMPONENT AND THE TOP OF THE GUARD SHALL BE |
| | LOCATED NOT LESS THAN 42 INCHES ABOVE THE ELEVATED |
| | SURFACE ADJACENT TO THE GUARD. THE GUARD SHALL BE |
| | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE |
| | LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2. PAGE A1 SHOWS THE EXHAUST TERMINATION POINT TO BE |
| | LESS THAN 5 FEET FROM THE PROPERTY LINE. THE |
| | TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO THE |
| | ATMOSPHERE CONVEYING FLAMMABLE VAPORS, FUMES OR DUSTS |
| | SHALL BE AT A MINIMUM: 30 FEET FROM THE PROPERTY LINE; |
| | 10 FEET FROM OPENINGS INTO THE BUILDING; 6 FEET FROM |
| | EXTERIOR WALLS AND ROOFS; 30 FEET FROM COMBUSTIBLE |
| | WALLS AND OPENINGS INTO THE BUILDING WHICH ARE IN THE |
| | DIRECTION OF THE EXHAUST DISCHARGE IN ACCORDANCE WITH |
| | FBCM 502.7.3.6. |
| | |
| | 3. NO SOURCE OR LOCATION OF MAKEUP AIR HAS BEEN |
| | IDENTIFIED ON THE PLANS. MAKEUP AIR SHALL BE PROVIDED |
| | AT A RATE APPROXIMATELY EQUAL TO THE RATE THAT AIR IS |
| | EXHAUSTED BY THE HAZARDOUS EXHAUST SYSTEM. MAKEUP-AIR |
| | INTAKES SHALL BE LOCATED SO AS TO AVOID RECIRCULATION |
| | OF CONTAMINATED AIR IN ACCORDANCE WITH FBCM 510.5.5. |
| | |
| | 4. PLEASE PROVIDE INFORMATION ON THE CROSS SECTIONAL |
| | INSIDE AREA OF THE BOOTH, PARTICULARLY IN THE DIRECTION |
| | OF AIRFLOW. VENTILATION SYSTEMS SHALL BE DESIGNED, |
| | INSTALLED AND MAINTAINED SUCH THAT THE AVERAGE AIR |
| | VELOCITY OVER THE OPEN FACE OF THE BOOTH, OR BOOTH |
| | CROSS SECTION IN THE DIRECTION OF AIRFLOW DURING |
| | SPRAYING OPERATIONS, IS NOT LESS THAN 100 FEET PER |
| | MINUTE IN ACCORDANCE WITH FBCM 502.7.3.3. IT CAN NOT BE |
| | DETERMINED AT THIS TIME IF THE PROPOSED RATE OF 7800 |
| | CFM WILL PRODUCE THE VELOCITY AS REQUIRED BY THIS |
| | SECTION. |
| | |
| | 5. PROVIDE WIND LOAD DATA SHOWING THE PROPOSED ROOFTOP |
| | SUPPORT SYSTEM IS SUFFICIENT TO RESIST WIND PRESSURES. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM 301.13. |
| | |
| | 6. SEVERAL SECTIONS OF THE SUBMITTAL PACKAGE ARE OF |
| | POOR QUALITY AND ILLEGIBLE. CONSTRUCTION DOCUMENTS |
| | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE IN ACCORDANCE WITH FBCB 106.1.1. PLEASE |
| | RESUBMIT DOCUMENTS WHICH ARE CLEAR AND LEGIBLE. |
| | |