2008-09-04 16:36:10REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE EXHAUST FAN ON THE ROOF APPEARS TO BE WITHIN 10
 FEET OF THE ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE
 FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET OF A ROOF EDGE IN ACCORDANCE
 WITH FBCM 304.10. THE GUARD SHALL EXTEND NOT LESS THAN
 30 INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT,
 FAN OR COMPONENT AND THE TOP OF THE GUARD SHALL BE
 LOCATED NOT LESS THAN 42 INCHES ABOVE THE ELEVATED
 SURFACE ADJACENT TO THE GUARD. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE
 LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2. PAGE A1 SHOWS THE EXHAUST TERMINATION POINT TO BE
 LESS THAN 5 FEET FROM THE PROPERTY LINE. THE
 TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO THE
 ATMOSPHERE CONVEYING FLAMMABLE VAPORS, FUMES OR DUSTS
 SHALL BE AT A MINIMUM: 30 FEET FROM THE PROPERTY LINE;
 10 FEET FROM OPENINGS INTO THE BUILDING; 6 FEET FROM
 EXTERIOR WALLS AND ROOFS; 30 FEET FROM COMBUSTIBLE
 WALLS AND OPENINGS INTO THE BUILDING WHICH ARE IN THE
 DIRECTION OF THE EXHAUST DISCHARGE IN ACCORDANCE WITH
 FBCM 502.7.3.6.
  
 3. NO SOURCE OR LOCATION OF MAKEUP AIR HAS BEEN
 IDENTIFIED ON THE PLANS. MAKEUP AIR SHALL BE PROVIDED
 AT A RATE APPROXIMATELY EQUAL TO THE RATE THAT AIR IS
 EXHAUSTED BY THE HAZARDOUS EXHAUST SYSTEM. MAKEUP-AIR
 INTAKES SHALL BE LOCATED SO AS TO AVOID RECIRCULATION
 OF CONTAMINATED AIR IN ACCORDANCE WITH FBCM 510.5.5.
  
 4. PLEASE PROVIDE INFORMATION ON THE CROSS SECTIONAL
 INSIDE AREA OF THE BOOTH, PARTICULARLY IN THE DIRECTION
 OF AIRFLOW. VENTILATION SYSTEMS SHALL BE DESIGNED,
 INSTALLED AND MAINTAINED SUCH THAT THE AVERAGE AIR
 VELOCITY OVER THE OPEN FACE OF THE BOOTH, OR BOOTH
 CROSS SECTION IN THE DIRECTION OF AIRFLOW DURING
 SPRAYING OPERATIONS, IS NOT LESS THAN 100 FEET PER
 MINUTE IN ACCORDANCE WITH FBCM 502.7.3.3. IT CAN NOT BE
 DETERMINED AT THIS TIME IF THE PROPOSED RATE OF 7800
 CFM WILL PRODUCE THE VELOCITY AS REQUIRED BY THIS
 SECTION.
  
 5. PROVIDE WIND LOAD DATA SHOWING THE PROPOSED ROOFTOP
 SUPPORT SYSTEM IS SUFFICIENT TO RESIST WIND PRESSURES.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM 301.13.
  
 6. SEVERAL SECTIONS OF THE SUBMITTAL PACKAGE ARE OF
 POOR QUALITY AND ILLEGIBLE. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE IN ACCORDANCE WITH FBCB 106.1.1. PLEASE
 RESUBMIT DOCUMENTS WHICH ARE CLEAR AND LEGIBLE.
  