| 2008-09-11 11:42:57 | ***DENIED*** |
| | |
| | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. |
| | |
| | 2) SPRAY BOOTH AND ASSOCIATED EQUIPMENT TO COMPY WITH |
| | NFPA 33. |
| | |
| | 3) SPRAY BOOTH AND APPLICABLE EQUIPMENT THAT CONVEY |
| | FLAMMABLE OR COMBUSTIBLE LIQUID SHALL BE BONDED AND |
| | GROUNDED. 33.6.7 |
| | |
| | 4) IN ADDITION TO OTHER DISTANCE REQUIREMENTS, SPRAY |
| | BOOTH SHALL BE SEPARATED FROM OTHER OPERATIONS BY A |
| | DISTANCE OF NOT LESS THAN THREE (3) FEET OR BY |
| | PARTITION, WALL OR FLOOR/CEILING ASSEMBLY WITH NOT LESS |
| | THAN ONE (1) HOUR FIRE RATING. 33.5.3 |
| | |
| | 5) PLANS INDICATE THAT THE SPRAY BOOTH WILL BE |
| | PROTECTED BY A DRY CHEMICAL SYSTEM, NFPA-17. PLEASE |
| | PROVIDE MORE INFORMATION ILLUSTRATING SYSTEM LAYOUT |
| | THAT PROTECTS THE BOOTH, EXHAUST PLENUM AND EXHAUST |
| | DUCTWORK. ADDITIONALLY, PROVIDE MANUFACTURER |
| | SPECIFICATION SHEETS. |
| | |
| | 6) SPRAY BOOTH SHALL BE CONNECTED TO THE BUILDING FIRE |
| | ALARM SYSTEM IF APPLICABLE. IF A FIRE ALARM SYSTEM IS |
| | NOT PROVIDED, A LOCAL ALARM FOR OCCUPANT NOTIFICATION |
| | IS STILL REQUIRED IN THE VICINITY OF SPRAYING |
| | OPERATION. |
| | |
| | 7) SHOW THE LOCATION OF AUTOMATIC SHUT DOWN. 33.9.2.1 |
| | (4) |
| | |
| | |
| | ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER |
| | INDICATING HOW AND WHERE ON THE PLANS EACH COMMENT WAS |
| | ADDRESSED WOULD HELP EXPEDITE THE PLAN REVIEW PROCESS. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |