Plan Review Notes
Plan Review Notes For Permit 08080493
Permit Number 08080493
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-03 10:56:15BUILDING PLAN REVIEW
 PERMIT: 08080493
 ADD: 1400 ALLENDALE RD
 CONT:IMPERIAL BUILDERS, INC
 TEL: (561)305-7388
 SEPTEMBER 03,2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 THE SPRAY BOOTH BROCHURE SUBMITTED IS ILLEGABLE PLEASE
 PROVIDE 2 COPIES THAT ARE CLEAR AND LEGIBLE.
 1B): PLEASE SUBMIT (2) OF ALL PLANS, REPORTS, REVISIONS
 , PRODUCT APPROVALS AND OR SUBMITTALS FOR REVIEW FOR
 PERMIT. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS AND 2004 EXISTING
 BUILDING CODE.
 2004 EXISTING BUILDING CODE SECTION 301.5 A DESIGN
 PROFESSIONAL MUST ELECT A LEVEL OF ALTERATION PURSUANT
 TO SECTION 303,304 & 305. PLANS FAIL TO INDICATE TO
 WHAT DESIGN CRITERIA THESE PLANS WERE TO BE DESIGNED
 TOO.
  
 2) PLANS FAIL TO INDICATE WIND ZONE INFORMATION:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE
 REGISTERED DESIGN PROFESSIONAL.
  
 3) THERE IS A DIFFERENCE BETWEEN TERMINOLOGY IN A SPRAY
 BOOTH AND SPRAY ROOM. THE 2004 FBC- BUILDING CODE
 COMMENTARY LIST THE PRIMARY DIFFERENCE BETWEEN A SPRAY
 ROOM AND A SPRAY BOOTH IS THAT SPRAY BOOTHS ARE
 PARTIALLY OPEN. WHEREAS A SPRAY ROOM IS TO BE ENCLOSED
 WITH FIRE BARRIER ASSEMBLIES HAVING A FIRE -RESISTANCE
 RATING OF AT LEAST 1-HR,
  
 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE
 WATERPROOFED AND DRAINED IN AN APPROVED MANNER.
  
 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL
 BE SO DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM.
 ALUMINUM SHALL NOT BE USED.
  
 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL . WHERE SUCH SPACES
 ARE NOT SEPARATELY ENCLOSED, NONCOMBUSTIBLE SPRAY
 CURTAINS SHALL BE PROVIDED TO RESTRICT THE SPREAD OF
 FLAMMABLE VAPORS.
  
 416.3.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE
 SMOOTH AND CONTINUOUS WITHOUT EDGES, AND SHALL BE SO
 CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR
 FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE
 WASHING AND CLEANING, AND SHALL BE SO DESIGNED TO
 CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM
 SHALL NOT BE USED.
  
 416.4 FIRE PROTECTION.
 AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE
 PROVIDED IN ALL SPRAY, DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9 .
  
 4) 903.2.13IN ADDITION TO THE REQUIREMENTS OF SECTION
 903.2 , THE PROVISIONS INDICATED IN TABLE 903.2.13 ALSO
 REQUIRE THE INSTALLATION OF A SUPPRESSION SYSTEM FOR
 CERTAIN BUILDINGS AND AREAS.
 903.2.13 TABLE 903.2.13 FLAMMABLE FINISHES.
  
 5) PLANS & BROCHURE DO NOT INDICATE IF THIS STRUCTURE
 WILL ALSO BE USED AS A DRYING ROOM NEEDING TO MEET THE
 REQUIREMENTS OF 417. PLEASE PROVIDE ADDITIONAL
 INFORMATION. 106.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.