| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | SAME COMMENTS AS THE PREVIOUS REVIEW: |
| | |
| | 1} THE SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR. |
| | PLEASE EXPOUND ON ADDED ELECTRICAL WORK AND INDICATE |
| | COMPLIANCE WITH CHAPTER 13 FBC. |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING |
| | OR A SEPARATELY METERED OR PERMITTED PORTION OF A |
| | BUILDING SHALL BE DETERMINED BY EITHER THE BUILDING |
| | AREA METHOD DESCRIBED IN SECTION 415.2.C.1 OR THE |
| | SPACE-BY-SPACE METHOD DESCRIBED IN SECTION 415.2.B.1. |
| | THE INSTALLED INTERIOR LIGHTING POWER IDENTIFIED IN |
| | ACCORDANCE WITH SECTION 415.2.ABC.1.1 SHALL NOT EXCEED |
| | THE INTERIOR LIGHTING POWER ALLOWANCE DEVELOPED IN |
| | ACCORDANCE WITH SECTION 415.2.C.1 OR 415.2.B.1. THIS |
| | CAN BE DEMONSTRATED ON THE PLANS INDICATING THE |
| | WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT |
| | CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES |
| | ON THE FIXTURE SCHEDULE.*** NONE OF THESE COMMENTS WERE |
| | RESPONDED TO, SUBMIT WRITTEN RESPONSE TO THE COMMENTS |
| | MADE IN THIS REVIEW. |
| | |