| Plan Review Notes For Permit 08080467 |
| Permit Number |
08080467 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-11 10:12:50 | ***DENIED*** | | | | | | 1) ILLUSTRATE FIRE SPRINKLER LAYOUT ON PLANS. | | | ADDITIONALLY, SEPARATE SHOP DRAWINGS AND PERMIT WILL BE | | | REQUIRED PRIOR TO INSTALLATION. | | | | | | 2) WILL A FIRE ALARM SYSTEM BE PROVIDED. IF SO, | | | ILLUSTRATE APPLICABLE EQUIPMENT SHOWING MINIMUM LEVELS | | | AND ADA REQUIREMENTS. | | | | | | 3) IN ADDITION TO FAN SHUT DOWN, DUCT SMOKE DETECTORS | | | SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|