Text |
| 2008-09-03 14:16:07 | |
| | |
| | |
| | |
| | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE TO COORDINATE ALL SYMBOLS ON |
| | PLANS WITH THE SYMBOL LEGEND. FOR EXAMPLE: PLEASE SEE |
| | THE COMMENTS FROM THE MECHANICAL REVIEW WITH RESPECT TO |
| | THE SMOKE DETECTORS FOR AC SYSTEM/DUCTS. |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION |
| | |
| | 2) NOTE: PLEASE BE SURE THE PLANS STATE 517 PART TWO. |
| | PLANS DO TALK ABOUT REDUNDANT GROUNDING HOWEVER THERE |
| | ARE OTHER REQUIREMENTS FOR WIRING IN THIS OCCUPANCY. |
| | |
| | 3) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING |
| | CODES; |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 ( WHERE APPLICABLE). |
| | |
| | PLANS MAY NOT STATE LATEST EDITION. |
| | |
| | 4) NOTE: THIS IS A SINGLE TENANT AS SHOWN, ONLY ONE |
| | METER IS PERMITTED. |
| | THIS ITEM IS NOT ADDRESSED IN THE NEC. THE RISER SHOWS |
| | A NEW 600AMP SERVICE CAPACITY HOWEVER NO LOAD |
| | CALCULATIONS WERE SUBMITTED FOR THE ENTIRE BUILDING. |
| | 220, 230.70, 240.4, 310.16 |
| | |
| | 5) NOTE: PLEASE PROVIDE NOTES PER |
| | 13-413.1.ABC.2.1,.2.2. |
| | |
| | 6) NOTE: PLEASE EXPLAIN HOW THE #6 AS SHOWN AS A |
| | GROUNDING ELECTRODE CONDUCTOR MEETS 250.66, 250.50 |
| | |
| | 7) NOTE: PLEASE VERIFY IF BUILDING WILL HAVE A FIRE |
| | ALARM SYSTEM. IF SO PLEASE SEE FBC 11-4.28.1,.2 AND .3 |
| | FOR MINIMUM LEVELS AND LOCATIONS OF DEVICES TO MEET ADA |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |