| 2008-09-03 09:16:53 | |
| | |
| | |
| | |
| | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE COORDINATE ALL CIRCUITING. PLEASE BE |
| | SURE TO LABEL PANELS. SOME CIRCUITING ON PLANS ARE NOT |
| | ON SCHEDULE(S). FOR EXAMPLE PLEASE SEE LIGHTING. |
| | PLEASE ALSO INDICATE ALL NEW LIGHTING CIRCUITS. SOME |
| | CIRCUITS ARE NOTED AS *NEW* ON SCHEDULES HOWEVER THE |
| | OTHERS ARE NOT. |
| | 408.4 |
| | FBC 106.1.1, 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE GO OVER LIGHTING PERFORMANCE |
| | CALCULATIONS. THERE ARE LEVELS SHOWN WHICH EXCEED TABLE |
| | WATTAGE ALLOWANCES. FOR EXAMPLE: A JANITOR CLOSET MAY |
| | NOT HAVE AN ALLOWANCE OF 1.5. PLEASE SEE 13-415.2.B |
| | THIS IS ONE EXAMPLE HOWEVER THERE ARE OTHERS. |
| | |
| | ** PLEASE KNOW IF THIS IS A SIMULATED EMERGENCY OR |
| | TRIAGE AREAS THIS IS NOT HOSPITAL OCCUPANCY WHERE |
| | ACTUAL TREATMENTS OR SURGERY WILL TAKE PLACE. HOWEVER |
| | IF SIMULATED USE AND EQUIPMENT IS BEING USED THERE MAY |
| | BE AN ALLOWANCE. AS THE SCOPE IS NOT CLEAR AT THIS TIME |
| | PLEASE CALL TO GO OVER. |
| | |
| | 3) NOTE: PLEASE PROVIDE NOTES ON PLANS FOR AREAS AND |
| | WIRING PER NEC 517 PART TWO. |
| | |
| | PLEASE PROVIDE DETAIL ON WHAT THESE AREAS MAY BE USED |
| | FOR. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |