2008-09-05 10:25:23BUILDING PLAN REVIEW
 PERMIT: 08080450
 ADD: 5205 GREENWOOD AVENUE SUITE# ______
 CONT: HEDRICK BROTHERS CONST
 TEL: (561603-7417
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPTEMBER 5TH, 2008
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) SHEET GV-102 PROJECT DATA IS MISSING PLANS
 SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER JULY
 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC BUILDING
 WITH THE 2007 SUPPLEMENTS.
  
 2) THE PERMIT APPLICATION DESCIPTION OF WORK INDICATES
 PHASE V, THERE SEEMS TO BE SOME DISCREPENCIES OR
 CLARIFICATION NEEDED AS TO WHERE THIS WORK WILL TAKE
 PLACE. THE PERMIT APPLICATION DOES NOT INDICATE AS TO
 FLOOR OR SUITE NUMBER.
 PHASE III AREA UNDER PERMIT # 07040621 WAS FOR THE 1ST
 FLOOR TENANT & COMMON AREAS. SHEET GV-101
 PHASE IV AREA UNDER PERMIT # 08020236 WAS FOR 2ND FLOOR
 PARTIAL DR. JONES OFFICE
 PHASE V SHOULD SHOW UP AS SUITE # 250 AS SHOWN ON SHEET
 AF-102 UNDER PHASE IV PERMIT# 08020236
 PLEASE MAKE CORRECTIONS
 SHEET AF-102 NOTE# 15 MAKES IT UNCLEAR AS TO WHAT WORK
 IS BEING PERMITED UNDER THIS PERMIT AS WELL AS
 ELEVATIONS THAT ARE ALASO NOT REQUIED FOR AN INTERIOR
 BUILD-OUT.
  
  
  
 3) SHEET AF-406 DETAIL# 3 INDICATES WHAT APPEARS TO BE
 A BREAK ROOM WITH MICROWAVE , DISHWASHER & KITHEN SINK.
 IF THIS AREA IS TO BE USED AS A BREAK AREA THEN
 ACCESSIBLITY ISSUES NEED TO BE ADDRESSED.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved