| 2008-08-26 10:12:45 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- THERE ARE TWO DIFFERENTDESIGN PRESSURES | | | CALCULATIONSSUBMITTEDBY TWO DIFFERENT ENGINEERS. | | | PROVIDE TWO COPIES OF ENGINEERING CALCULATIONS FROM ONE | | | ENGINEER ONLY. | | | NOTE: ENGINEERCALCULATIONS ARE NOT REQUIRED. | | | CONTRACTORMAY USE TABLE R301.2(2) OF 2004 FLORIDA | | | RESIDENTIALCODE TO OBTAIN THE DESIGN PRESSURES. | | | | | | 2- PROVIDE A COMPLETE INSTALLATION SCHEDULE AS REQUIRED | | | BYTHE CITY IMPLEMENTATION STANDARD FOR WIND-BORNE | | | DEBRIS IMPACT PROTECTION.SEE ATTACHED SAMPLE. | | | ***NOTE:WHEN FILLING UPTHE INSTALLATION SCHEDULE | | | MAKE SURE CORRECT ANCHOR SCHEDULE IS REFERENCED.FOR | | | EXAMPLE, CONCRETE ANCHOR SCHEDULE MAY NOT BE USED FOR | | | CONCRETE BLOCK CONSTRUCTION UNLESS PROPER TESTING IS | | | PROVIDED SHOWING THATTHE SUBSTRATETORECEIVE THE | | | ACCORDIONSHUTTERS IS POURED CONCRETE WITH MIN. 3,100 | | | PSI STRENGTH. | | | | | | JULIO GOMEZ | | | BUILDING PLAN EXAMINER | | | (561)805-6712 |
|