| | ** DENIED 3RD REVIEW ** |
| | ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS |
| | WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE |
| | NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO |
| | MEET MINIMUM CODES. |
| | |
| | STORE #319 831 VILLAGE BLVD. |
| | |
| | |
| | 1) NOTE: THE PLANS SHOW A GEN PANEL LOCATED IN THE SAME |
| | ROOM AS OTHER ELECTRICAL SYSTEMS. PLEASE SEE NFPA-110 |
| | 7.2.2. THIS IS BASED ON THE DEFINITIONS WHICH INCLUDES |
| | ALL EPSS EQUIPMENT UP TO THE LOAD SIDE OF THE TRANSFER |
| | SWITCH THIS GEN PANEL MAY NOT BE IN THE SAME ROOM WITH |
| | OTHER EQUIPMENT. PLEASE SEE 2002 NFPA-110. |
| | PLEASE SEE ELECTRICAL ROOM PLANS ON E-7 WHICH SEEMS TO |
| | INDICATE A * LIFTER SWITCH*. WHAT IS THIS? PLEASE SEE |
| | NFPA-110 |
| | |
| | 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE |
| | HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE |
| | INFORMATION. BASED ON THE RISER AND PANELS, THERE IS |
| | OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED |
| | SYSTEMS IN THE SAME EQUIPMENT. |
| | THE GEN PANEL WOULD BE REQUIRED TO MEET 700.9 AS A |
| | SWITCHBOARD. SEE COMMENTARY AS A SWITCHBOARD WOULD |
| | PROVIDE THE REQUIRED SEPARATION. PLEASE KNOW THAT BASED |
| | ON COMMENT NUMBER ONE ABOVE THE LOCATION OF THIS GEN |
| | PANEL NEEDS TO BE ADJUSTED OR RISER NEEDS TO BE REVISED |
| | TO SHOW DIFFERENT EQUIPMENT. THERE ARE OTHER OPTIONS |
| | HOWEVER THIS IS ONLY NOTED BY REVIEWER AS NEEDING TO |
| | MET MINIMUM CODES. |
| | SYSTEMS NEED TO BE LABELED ACCORDINGLY SUCH AS * |
| | OPTIONAL STAND-BY AND LIFE SAFETY. BASED ON PANEL |
| | SCHEDULES SUBMITTED THERE IS LIFE SAFETY, LEGALLY |
| | REQUIRED AND OPTIONAL STAND-BY LOADS. |
| | NO PANEL SCHEDULE WAS SUBMITTED FOR E-1 WHICH IS FED |
| | FROM E SO THOSE LOADS CAN NOT BE DETERMINED TO BE |
| | 700,701, OR 702 SYSTEM LOADS. |
| | THERE ARE MANY OTHERS. |
| | |
| | *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT |
| | DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS |
| | SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO |
| | THE CITY OF WEST PALM BEACH. |
| | ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED, |
| | THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE |
| | PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE |
| | CONTACT/MEETING HAS BEEN HELD. |
| | |
| | 3) NOTE: PLEASE TAKE A LOOK AT THE SIZE OF THE JUNCTION |
| | BOX WITH THE FEEDERS ALONG WITH CONTROL CIRCUITS. THE |
| | FEEDERS GO INTO AND OUT OF THIS BOX ALONG WITH OTHER |
| | CONDUCTORS. THE PLANS STATE PULL BOX ONLY HOWEVER |
| | PLEASE BE SURE TO SEE 314.28 AS ANY VARIATION IN THESE |
| | AS SHOWN MAY INCREASE. THIS IS NOTED ONLY BASED ON |
| | OTHER COMMENTS THERE MAY BE A NEED FOR A CHANGE. |
| | PLEASE ALSO SEE EMERGENCY GENERATOR NETWORK CABLING AS |
| | THE CONDUCTORS SHOWN ON RISER ARE NOT THE SAME. AN |
| | EXAMPLE IS THE #14 ON RISER AND DETAIL SHOWS ALL #12? |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE, |
| | ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE |
| | MORE THAN ONE. |
| | ENCLOSURES SHALL MEET NFPA-110 7.2.1.1 |
| | NEC 110.3, 700.6, 90.7 ETC |
| | |
| | 5) NOTE: FUEL STAND-BY TIME, CAPACITY, SIZING ETC NEEDS |
| | TO BE ON PLANS. MINIMUM TIMES ARE STATED IN NFPA-110 |
| | CHAPTER 4 ALONG WITH NEC 700.12 |
| | |
| | 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR |
| | FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN |
| | 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL |
| | BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE |
| | PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS |
| | NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE |
| | COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT |
| | MEET 225.38, 225.39. |
| | THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD |
| | SERVED. |
| | ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR |
| | MAY OR MAY NOT MEET READILY ACCESSIBLE DEPENDING ON |
| | LOCKED ENCLOSURE, FENCING AROUND ENCLOSURE ETC.. |
| | |
| | 7) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL |
| | BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY |
| | AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD |
| | CREATE A SAFETY ISSUE. |
| | OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH |
| | AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE |
| | LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING |
| | PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING |
| | INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2 |
| | NEW OUTSIDE LIGHTS INDICATE CONTROLS PER ENERGY |
| | MANAGEMENT SYSTEM HOWEVER PLEASE SEE 13-415.1.ABC.1.4. |
| | DOES THIS PROVIDE 10HRS MINIMUM BACK UP FOR SCHEDULING |
| | OR MEET PHOTO-SENSOR REQUIREMENTS? IF THIS WAS THE ONLY |
| | ITEM IT WOULD HAVE BEEN REDLINED. |
| | |
| | 8) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002. |
| | |
| | 9) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR |
| | GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF |
| | NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED |
| | FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE |
| | PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER |
| | REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS |
| | EXAMINERS. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |