Plan Review Notes
Plan Review Notes For Permit 08080402
Permit Number 08080402
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-19 13:37:01** DENIED SECOND REVIEW **
  
 ** PLEASE SEE NOTES BELOW AS THEY ARE EXACT COMMENTS
 FROM PREVIOUS REVIEW.
  
  
  
 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE
 SUBMITTED MEETING PRESCRIPTIVE REQUIREMENTS. 13-415.2,
 13-415.2.ABC.1.1,.1.2,.1.3 ETC
 THIS WAS GONE OVER AT LENGTH IN MEETING HELD WITH
 DESIGNER FROM FIRM YET THE PLANS ARE RESUBMITTED WITH
 NO CALCULATIONS.
  
 2) NOTE: PLANS STILL DO NOT SHOW ANY COMPLIANCE FOR
 PRESCRIPTIVE REQUIREMENTS FOR NEW AREAS AND NEW
 LIGHTING CONTROLS FOR SEPARATE SPACES. THIS COMMENT WAS
 FOR NEW AREAS ONLY AND COMMENTS WERE GONE OVER WITH
 DESIGNER FROM FIRM AT LENGTH. HOWEVER PLANS STILL ONLY
 SHOW STANDARDS DEVICES AND NO COMPLIANCE FOR NEW IS
 SHOWN.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: NO LETTER WAS SUBMITTED WITH RESPECT TO
 REQUIRED LIGHTING FOR EGRESS OR OCCUPANCY NOT PERMITTED
 WHEN UNDER EMERGENCY POWER. THIS WAS ALSO GONE OVER AT
 LENGTH IN MEETING YET NO CHANGES IN PLANS OR STORE
 OPERATIONS ARE PROVIDED.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME HOWEVER PLEASE SEE COMMENTS
 ABOUT AS SOME SECTIONS HAVE NOW BEEN REAPEATED TWICE.
  
 6) NOTE: THE RISER AS SHOWN DOES NOT INCLUDE THE MOST
 RECENT ELECTRICAL REVISIONS AS MADE ON SITE WITH THE
 MOST RECENT PERMITTED ELECTRICAL WORK. THIS WILL NEED
 TO BE REVISED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  