2008-09-03 16:06:55REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. STRUCTURAL PLANS SHOW A DETAIL FOR NEW CONDENSER #8.
 THE HEIGHT OF THE CONDENSER ABOVE THE ROOF SURFACE IS
 NOT SHOWN ON THE PAGE S-2 DETAILS. SHOW THE MINIMUM
 REQUIRED CLEARANCE FROM THE ROOF SURFACE ON THE PLANS
 IN ACCORDANCE WITH FBCB TABLE 1509.7.
  
 2. PAGE S-2 GENERAL NOTE #6 CALLS FOR DETAIL SHOWING
 HOW THE APPLIANCE IS TO BE ATTACHED TO THE STAND TO
 MEET WIND RESISTANCE REQUIREMENTS. NO SUCH DETAIL OR
 SHOP DRAWING WAS PROVIDED. PROVIDE MISSING INFORMATION
 TO DEMONSTRATE COMPLIANCE WITH THE WIND RESISTANCE
 REQUIREMENTS OF FBCM 301.13 FOR ATTACHMENT TO THE
 STRUCTURE.
  
 3. IN ADDITION TO THE ABOVE REQUIREMENTS, PROVIDE
 DOCUMENTATION FROM THE MANUFACTURER OF CONDENSER #8
 SHOWING THAT THE APPLIANCE ITSELF IS DESIGNED TO RESIST
 WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 4. PAGE M-3 NOTE ON ROOF PLAN INDICATES THAT THE NEW
 AC-1 AND NEW AC-2 WILL FIT ON THE EXISTING ROOF CURB.
 HOWEVER, DETAIL 7 ON PAGE M-4 CALLS FOR A CURB ADAPTER
 FOR NEW AC UNITS. WHICH IS CORRECT? PLEASE CLARIFY IN
 ACCORDANCE WITH FBCB 106.1.1. ADJUST ATTACHMENT DETAIL
 AND NOTES SO PLANS ARE COORDINATED AND SHOW AN
 ATTACHMENT DETAIL WHICH IS IN COMPLIANCE WITH FBCM
 301.13.
  
 5. PROVIDE DOCUMENTATION FROM THE MANUFACTURER OF AC-1
 AND AC-2 SHOWING THESE APPLIANCES ARE DESIGNED TO
 RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 6. PAGE M-4: DETAIL #8 SHOWS GALVANIZED STRAPS OVER F-6
 TO SECURE THE FAN FOR WIND LOADS. THIS FAN IS AN
 UPBLAST FAN, NOT A DOWN DISCHARGE FAN AS SHOWN IN THIS
 DETAIL. STRAPS OVER AN UPBLAST GREASE EXHAUST FAN WILL
 ACCUMULATE GREASE AND DIVERT IT TO LOCATIONS OTHER THAN
 THE GREASE RESERVOIR SUPPLIED WITH THE FAN. THIS HAS
 THE POTENTIAL TO CREATE AN ADDITIONAL FIRE HAZARD ON
 THE ROOF. IT IS ALSO UNCLEAR HOW THESE STRAPS WILL
 INTERACT WITH THE HINGE MECHANISM ON THE GREASE EXHAUST
 FAN AS REQUIRED IN ACCORDANCE WITH FBCM 506.5.3.
 NOTE: THERE ARE GREASE EXHAUST FANS AND CURBS WHICH ARE
 DESIGNED TO RESIST WIND PRESSURES WITHOUT THE USE OF
 ADDITIONAL, FIELD INSTALLED STRAPPING WHICH WILL AVOID
 INTERFERENCE WITH GREASE EXHAUST DISCHARGE. THIS MAY BE
 A PREFERABLE (TO THE DESIGN PROFESSIONAL OR OWNER)
 MEANS OF ACCOMPLISHING COMPLIANCE WITH THESE CODE
 PROVISIONS.
  