| 2009-04-02 18:26:29 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | NFPA-58 |
| | |
| | A. SHT P-3 & P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF |
| | ITS SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE |
| | LOCATED SO THAT THE FILLING CONNECTION AND FIXED |
| | MAXIMUM LIQUID LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY |
| | EXTERNAL SOURCE OF IGNITION. SEE TABLE 6.3.9. TANK IS A |
| | MAXIMUM 7 FT TO THE FAR SIDE OF THE GENERATOR. |
| | |
| | B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE |
| | GAS PERMIT REQUIRED: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC |
| | TRANSFER VALVE AND SHUT OFF VALES. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT |
| | WILL BE REMOVED. |
| | |
| | 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC |
| | TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS |
| | TO NATURAL GAS. |
| | |
| | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS PHM-001 THRU PHM-016. A TITLE BLOCK SHALL BE |
| | USED ON EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS |
| | AND LICENSE NUMBER OF THE ENGINEER OR IF APPLICABLE, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND IF |
| | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING |
| | BUSINESS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. FAC |
| | 61G15-23.002(2) & FS 471.025. |
| | |
| | 2. ALL SHTS WITH MOFFATT & NICHOL TITLE BLOCKS. THE |
| | ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE, |
| | (3780 KILROY AIRPORT WAY LONG BEACH CALIFORNIA), DOES |
| | NOT REFLECT THE ADDRESS IN THE TITLE BLOCKS, (1509 W. |
| | SWANN AVE. TAMPA FLORIDA). FAC 61G15-23.002(2) & FS |
| | 471.025. PLEASE UPDATE TITLE BLOCKS OR THE DBPR WEBSITE |
| | PRIOR TO RESUBMITTING TO THE CITY WPB FOR REVIEW. (THE |
| | ADDRESS ON THE DBPR WEBSITE CAN BE ADDED TO THE TITLE |
| | BLOCK OF EACH SHEET TO COMPLY WITH THIS REQUIREMENT). |
| | |
| | 3. SHT G-003 CODE DESIGN CRITERIA SHALL INCLUDE THE |
| | FBC-2004 WITH 2007 REVISIONS. SECTION 106.1.1. |
| | |
| | 4. THE WATER SUPPLY TO THE DOCKS SHALL BE PROTECTED |
| | FROM BACKFLOW PER SECTION 608.13.2. PLEASE INDICATE THE |
| | RPZV BACKFLOW LOCATION FOR EACH DOCK OR IF ALL DOCKS |
| | ARE CONNECTED TO ONE METER INDICATE ON PLANS THE |
| | LOCATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |