Plan Review Notes
Plan Review Notes For Permit 08080402
Permit Number 08080402
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-19 15:29:49***DENIED***
  
 1) BUILDING CODE ANALYSIS INDICATES NFPA, 2003 EDITION.
 LIST SPECIFIC NFPA STANDARD.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) BUILDING CODE ANALYSIS LISTS PROJECT AS EXISTING
 MERCANTILE. SECTION 7.4.1.2 APPLIES TO MEANS OF EGRESS
 OTHER THAN EXISTING BUILDINGS.
  
 4) EXIT SIGNS SHALL BE PROVIDED AT DISTANCES NOT TO
 EXCEED 100'.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 6) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 HOOD/SUPPRESSION SYSTEM.
  
 7) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 8) CLARIFY SCOPE OF WORK REGARDING FIRE ALARM SYSTEM
 AND SHOW ALL EQUIPMENT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756