| 2008-09-04 11:32:29 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 2, REVISED PLUMBING RISER: PLEASE CORRECT THE |
| | FOLLOWING ITEMS PER THE FBC-2004 PLUMBING CODE |
| | SECTIONS. |
| | |
| | A} THE SHOWER AND TUB REQUIRE A VENT. PER SECTION |
| | 901.2.1 VENTING REQUIRED. |
| | |
| | B} SIZE THE WASTE ARMS AND WATER-SEAL TRAPS FOR THE |
| | LAVATORIES. PER SECTION 701.1 SCOPE AND (W.P.B. AS |
| | AMENDED) SECTION 106.3.5.4(9) PLUMBING. |
| | NOTE: IF THE WATER-SEAL TRAPS FOR THE LAVATORIES ARE |
| | 1-1/4" A CLEANOUT SHALL BE REQUIRED AT THE BASE OF THE |
| | STACK (PER SECTION 708.3.4 BASE OF STACK), HOWEVER PER |
| | SECTION 708.7 MINIMUM SIZE, EXCEPTION (1) IF THE |
| | WATER-SEAL TRAP IS 1-1/2" WITH SLIP JOINT OR GROUND |
| | JOINT CONNECTIONS A CLEANOUT IS NOT REQUIRED. |
| | |
| | C} CLEARLY INDICATE THE FLOW ON THE LAVATORY WASTE |
| | STACK. IT APPEARS TO BE GOING THE WRONG WAY. PER |
| | SECTION 706.3 INSTALLATION OF FITTINGS. FITTINGS SHALL |
| | BE INSTALLED TO GUIDE WASTE IN THE DIRECTION OF FLOW. |
| | |
| | D} CORRECTLY IDENTIFY THE FIXTURES IN THE BATHROOM AS |
| | LAVATORIES (LAV) NOT SINKS. PER SECTION 401.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |