| Plan Review Notes For Permit 08080371 |
| Permit Number |
08080371 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-21 14:43:27 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLAN A-0 APPLICABLE CODE INFORMATION STATES 'FLORIDA | | | STATE CODE 2001' THE PERMIT BEING APPLIED FOR IS UNDER | | | THE 2004 FBC WITH 2007 SUPPLEMENTS, PLEASE CORRECT | | | PLAN. | | | | | | 2) PLEASE ADD A DETAIL TO THE MECHANICAL PLANS FOR THE | | | INSTALLATION OF THE FIRE DAMPERS. PER 2004 FBC/M THE | | | SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE | | | DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER | | | SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING | | | PLANS BY THE DESIGNER. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|