| 2008-09-03 16:22:57 | BUILDING PLAN REVIEW |
| | PERMIT: 08080371 |
| | ADD: 250 S. AUSTRALIAN AVE #600 |
| | CONT: FISHER CONTRACTING CORP. |
| | TEL: (561)691-4716 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) SHEET A-0 MAKES REFERENCE TO THE 2001 CODE. PLANS |
| | SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER JULY |
| | 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC BUILDING |
| | WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | 5) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE EXISTING |
| | FLOOR LAYOUT, AND A PROPOSED FLOOR PLAN SHOWING ALL |
| | CHANGES TO THE EXISTING FLOOR PLAN. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE. FBC 106.1.1 |
| | |
| | 6) SHEET FP1.1. ANY PENETRATION THROUGH THE FIRE |
| | PARTITION SHALL MEET THE REQUIREMENTS OF FBC 712.3.1.2. |
| | PROVIDE THE UL ASSEMBLY DETAIL AND THE UL NUMBER FOR |
| | ALL PENETRATIONS (FIRE SPRINKLER PIPES) OF THE NEW FIRE |
| | WALL: SHOW ALL DETAILS ON THE PLANS. |
| | |
| | 7) SHEET A-1 MAKES REFERENCE TO DETAIL #2 ON THE SHEET, |
| | HOWEVER, DETAIL #2 REFERS TO THE FINISH SCHEDULE. ON |
| | THIS SAME SHEET DOOR TYPE ?B? DOES NOT INDICATE THE |
| | RATING (HOUR) OF THE DOOR. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |