| 2008-08-15 11:54:04 | ****************PROVISO**************** | | | A} IF DRYER ROOM IS A CONFINED SPACE, OPENINGS | | | REQUIRED PER SECTION 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. MINIMUM 1,000 CUBIC FEET REQUIRED. | | | | | | B}IF WATER HEATER ROOM IS A CONFINED SPACE, OPENINGS | | | REQUIRED PER SECTION 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. MINIMUM 3,750 CUBIC FEET REQUIRED. | | | | | | C} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|