| 2009-03-26 15:46:35 | ** DENIED REVIEW ** |
| | |
| | *** PLEASE SEE ALL NOTES ISSUED ON PROVISO DATED |
| | 12/18/08. MOST OF THESE COMMENTS STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1) NOTE: CIRCUITING ON PLANS NEEDS TO COORDINATE WITH |
| | ALL PANEL SCHEDULES AND ALL ELECTRICAL ON PLANS NEEDS |
| | TO BE CIRCUIT. SOME EXAMPLES WILL BE GIVEN. |
| | |
| | FOR EXAMPLE: PLEASE SEE LIGHTING FIXTURES IN AREA 931 |
| | WHICH DO NOT SHOW ANY CONTROLS OR CIRCUITING. |
| | THIS WILL ALSO BE NOTED FOR FBC CHAPTER 13 COMMENTS |
| | WITH RESPECT TO MINIMUM LIGHTING CONTROLS REQUIRED. |
| | |
| | FOR EXAMPLE: PLEASE SEE LIGHTING OUTSIDE 918 AND 919 IN |
| | HALLWAY WHICH DO NOT INDICATE ANY CONTROLS OR |
| | CIRCUITING. |
| | THIS WILL ALSO BE NOTED FOR FBC CHAPTER 13 COMMENTS |
| | WITH RESPECT TO MINIMUM LIGHTING CONTROLS REQUIRED. |
| | |
| | FOR EXAMPLE: PLEASE SEE CIRCUITS L9L29 THIS DOES NOT |
| | CORRELATE WITH THE ROOM/AREA DESIGNATION ON PLANS AND |
| | PANEL SCHEDULES. ANOTHER WOULD BE L9L14, L9L28, THESE |
| | ARE SOME EXAMPLES AND ARE NOT ALL. |
| | |
| | 408.4. |
| | FBC 106.1.2, 106.1.1, 106.5 |
| | |
| | 2) NOTE: AS NOTED ABOVE WITH RESPECT TO LIGHTING |
| | CONTROLS THERE ARE LIGHTING FIXTURES WHICH DO NOT |
| | INDICATE LIGHTING CONTROLS MEETING FBC |
| | 13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE PREVIOUS NOTES WITH RESPECT TO KEYPADS AND |
| | INFORMATION NEEDED. |
| | PLEASE PROVIDE. |
| | |
| | 3) NOTE: PLEASE VERIFY NEW RECEPTACLES FOR |
| | COPIERS/PRINTERS. CIRCUITS L9L23, AND L9R15 BOTH APPEAR |
| | TO BE FOR COPIERS HOWEVER ONE IS NOTED FOR A PRINTER? |
| | THIS DOES NOT ACCURATE. |
| | 4108.4, 220, 240.4 ETC. |
| | |
| | 4) NOTE: PLEASE CORRELATE RISER WITH PANEL SCHEDULES |
| | AND PLANS. |
| | FOR EXAMPLE: THE RISER INDICATES PANELS 8L AND 8LA, |
| | HOWEVER THE PANEL SCHEDULES SUBMITTED ARE FOR L9L, L9R, |
| | L9LA. |
| | THERE ARE NOT ANY OF THESE PANELS ON RISER. IN FACT |
| | WHAT IS L9LA? |
| | THE RISER INDICATES A 24CIRCUIT PANEL OF SOME SORT FROM |
| | 8L HOWEVER THIS CAN ONLY BE ASSUMED TO BE THE LIGHTING |
| | CONTROL PANEL. AS THE PANEL SCHEDULE ONLY STATES SUB |
| | PANEL ON L9L IT IS NOT CLEAR. |
| | THIS ALSO NOW INCLUDES WORK ON THE 8TH FLOOR WHICH WAS |
| | NOT PART OF ORIGINAL PLANS, PANEL SCHEDULES, RISER ETC. |
| | PANEL *H* WHICH IS ONLY NOW BEING SUBMITTED FOR THE |
| | FIRST TIME TO REVIEW IS SHOWN AS 120/208 YET RISER |
| | CLEARLY INDICATES THIS AS 277/480V. |
| | NOTE MENTIONS LOADS ON PANELS WERE NOT KNOWN HOWEVER |
| | BASED ON THE INITIAL DATE GIVEN ON PROVISO, LOADS MOST |
| | CERTAINLY COULD HAVE BEEN RECORDED AND INDICATED. |
| | |
| | PLEASE COORDINATE ALL PLANS, CIRCUITS, PANELS, RISER AS |
| | NOTED ON ORIGINAL PROVISO. |
| | 408,215.5, 220,310,ETC GIVEN AS SOME GENERAL CODE |
| | SECTIONS. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS PROVISO NOTES FOR |
| | COMPLIANCE WIHT FBC 11-4.28.1, .2 AND .3. NOT |
| | ADDRESSED. SEE SEPARATE NOTES PRINTED OUT AND ATTACHED |
| | FROM PROVISO. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |