| 2008-12-05 17:09:14 | |
| | ** DENIED REVIEW ** |
| | |
| | ** A CALL WAS PLACED TO THE ELECTRICAL DESIGNER FOR |
| | CORRECTIONS. EVERY ITEM ON PLANS WAS GONE OVER WITH |
| | PETE RUSSO. |
| | |
| | |
| | |
| | |
| | |
| | 1) NOTE: CIRCUITING ON PLANS FOR NEW ITEMS NOT COMPLETE |
| | AT THIS TIME. MANY ARE NOT LABELED NEW OR EXISTING. |
| | SOME ITEMS ON LIGHTING PLANS ARE NOT SHOWN AS NEW OR |
| | EXISTING. SOME DO NOT SHOW REQUIRED CONTROLS PER |
| | CHAPTER 13. |
| | NOTES NEED ADJUSTING. |
| | 408.4,310.16.240.4,13-415.1.ABC.1.1,.1.2, .1.3 ETC. |
| | |
| | 2) NOTE: CANDELA LEVELS FOR STROBES NOT PER FBC |
| | 11-4.28.3(4). 75MIN |
| | |
| | 3) NOTE: COORDINATION OF PHONE, DATA, ETC NEEDED. |
| | |
| | 4) NOTE: AS REQUESTED ON PREVIOUS REVIEW PLEASE REMOVE |
| | OLD/VOIDED SHEETS AND INSERT NEW SHEETS INTO COMPLETE |
| | SETS. THIS WAS DONE BY THIS REVIEWER THIS TIME. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |