| 2008-10-29 11:22:45 | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW** |
| | |
| | |
| | ** THERE ARE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE |
| | STILL IN NEED OF BEING ADDRESSED. |
| | |
| | |
| | |
| | 1) NOTE: PREVIOUS REVIEW NOTE #2 WITH RESPECT TO |
| | LIGHTING CONTROLS AND PROPOSED SYSTEM. AN OCCUPANT IS |
| | REQUIRED TO SEE ALL LIGHTING WHICH IS BEING CONTROLLED |
| | BY THE CONTROL DEVICE WHICH IS INDICATED AS SOME SORT |
| | OF *KEYPAD*. THE OTHER OPTION IS TO MEET THE EXCEPTION |
| | TO THE SECTION OF THE CODE HOWEVER THE PLANS DO NOT |
| | SHOW NAY DETAILS OF THE SYSTEM. |
| | PLEASE LIST SCHEDULING. |
| | PLEASE LIST MAXIMUM OVER RIDE TIMES WITH THE AUTOMATIC |
| | SHUT OFF OF LIGHTING. |
| | PLEASE SEE THE PLANS DO NOT INDICATE ANY INDICATOR |
| | PANEL/PILOT LIGHTS WITH NOTES FOR LABELING ETC |
| | PLEASE SEE NO MAXIMUM TIMES ARE LISTED. |
| | PLEASE INCLUDE THE SYSTEM DETAILS. |
| | 13-415.1.ABC.1.1, .1.2, .1.3. |
| | ** PLEASE SEE THE PANEL SCHEDULE FOR CIRCUITS L9L22 AND |
| | 24 WHICH NOTE NEW INCANDESCENT LIGHTING YET THE PLANS |
| | DO NOT INDICATE ANY OF THESE. IN FACT THE ROOM 914 |
| | (BASED ON ARCHITECTURAL PLANS) SHOWS A JUNCTION BOX |
| | HOWEVER NO ALLOWANCE FOR A FIXTURE. |
| | PLEASE INCLUDE OTHER SINGLE FLUORESCENT FIXTURE IN |
| | ROOM. |
| | *** ROOM DESIGNATION LAYER DID NOT PRINT ON THE |
| | ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4. THE PANEL |
| | ON THE SECONDARY SIDE OF THE TRANSFORMER DOES NOT MEET |
| | 408.36,240.21,310.16.240.4 ETC |
| | THE PANEL IS STILL SHOWN AS A 225AMP MLO PANEL. |
| | SECTIONS AS NOTED REQUIRE A MAIN TO BE INSTALLED. |
| | PLEASE BE SURE TO SEE THE FOLLOWING COMMENT WITH |
| | RESPECT TO THE SIZE OF THE MAIN PERMITTED. |
| | ** |
| | THE RESPONSE MENTIONS THIS WAS INSTALLED AND INSPECTED |
| | PREVIOUSLY OVER THE YEARS. BASICALLY STATING THEREFORE |
| | IT IS ACCEPTABLE AND IT SHOULD BE ACCEPTABLE TO |
| | CONTINUE WITH THIS VIOLATION OF CODE AND LIFE SAFETY |
| | ISSUES. |
| | THESE ARE NOT ONLY CLEAR VIOLATIONS HOWEVER THIS |
| | CREATES A LIFE SAFETY AND FIRE HAZARD. THE OCCUPANT MAY |
| | RECEIVE A WRITTEN CORRECTION NOTICE AT ANY TIME WHETHER |
| | OR NOT THE WORK WAS OR WAS DONE WITH PERMITS, PLANS, |
| | AND/OR INSPECTIONS. IF THE CORRECTION TO THE EQUIPMENT |
| | IS NOT A COURSE OF ACTION DESIRED PLEASE LET THIS |
| | OFFICE KNOW AND AN ON-SITE PRE-INSPECTION WILL TAKE |
| | PLACE. A CORRECTION NOTICE BY THIS OFFICE AS WELL AS |
| | THE FIRE MARSHAL OFFICE WILL BE ISSUED. THESE ARE NOT |
| | NEW CODES IN FACT THESE CODES GO BACK MANY CODE CYCLES |
| | EVEN WHEN THIS BUILDING WAS CONSTRUCTED. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW #5 WITH RESPECT TO |
| | THE CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER |
| | AS SHOWN NOT MEETING 240.21,310.16,240.4 ETC. |
| | THE CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER |
| | ARE TAPPED CONDUCTORS BY WHICH 240.21 REQUIRES |
| | TERMINATION IN OVER CURRENT PROTECTION. AS THE PANEL IS |
| | SHOWN AS A MAIN LUG ONLY (MLO) PANEL THERE IS NOT OVER |
| | CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE |
| | CONDUCTORS. AS NOTED ABOVE IN NOTE #2 SECTION 408.36 OF |
| | THE NEC REQUIRES A MAIN. PLEASE BE SURE TO SIZE MAIN |
| | ACCORDING TO LOAD AND THE PROTECTION OF THE CONDUCTORS |
| | WHICH ARE SHOWN AS 1/0. PLEASE SEE 310.16,240.4 FOR |
| | SIZING. |
| | ** |
| | ** |
| | THE RESPONSE MENTIONS THIS WAS INSTALLED AND INSPECTED |
| | PREVIOUSLY OVER THE YEARS. BASICALLY STATING THEREFORE |
| | IT IS ACCEPTABLE AND IT SHOULD BE ACCEPTABLE TO |
| | CONTINUE WITH THIS VIOLATION OF CODE AND LIFE SAFETY |
| | ISSUES. |
| | THESE ARE NOT ONLY CLEAR VIOLATIONS HOWEVER THIS |
| | CREATES A LIFE SAFETY AND FIRE HAZARD. THE OCCUPANT MAY |
| | RECEIVE A WRITTEN CORRECTION NOTICE AT ANY TIME WHETHER |
| | OR NOT THE WORK WAS OR WAS DONE WITH PERMITS, PLANS, |
| | AND/OR INSPECTIONS. IF THE CORRECTION TO THE EQUIPMENT |
| | IS NOT A COURSE OF ACTION DESIRED PLEASE LET THIS |
| | OFFICE KNOW AND AN ON-SITE PRE-INSPECTION WILL TAKE |
| | PLACE. A CORRECTION NOTICE BY THIS OFFICE AS WELL AS |
| | THE FIRE MARSHAL OFFICE WILL BE ISSUED. THESE ARE NOT |
| | NEW CODES IN FACT THESE CODES GO BACK MANY CODE CYCLES |
| | EVEN WHEN THIS BUILDING WAS CONSTRUCTED. |
| | |
| | 4) NOTE: PLEASE SEE THE RISER SHOWS SOME DIFFERENCES IN |
| | THE PANELS. RISER AND PANEL SCHEDULES INDICATE TWO |
| | PANELS. ONE L9L AND ONE L9R. YET RISER STILL SHOWS TWO |
| | L9L. PLEASE ADJUST MISPRINT. |
| | NO PANEL SCHEDULE SUBMITTED FOR THE HIGH VOLTAGE |
| | (277/480V PANEL). IT IS BEING ASSUMED NO WORK IS BEING |
| | PERFORMED IN THAT PANEL. |
| | PLEASE SEE SOME CIRCUITS ON PLANS SEEM TO CONTAIN A |
| | NUMERICAL CIRCUIT NUMBER WHICH IS NOT ON EITHER PANEL |
| | SCHEDULE. FOR EXAMPLE SEE LOBBY AREA TABLE WHICH SHOWS |
| | A L9L62. |
| | PLEASE SEE OTHER ROOMS SUCH AS ROOM 904 WHICH HAS NEW |
| | RECEPTACLES SHOWN HOWEVER NO NEW CIRCUITING INDICATED. |
| | ** THERE ARE OTHERS. |
| | 408.4,310.16 |
| | FBC 106.1.1, 106.1.2 |
| | |
| | |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #5. PLEASE |
| | SHOW AND INDICATE ALL MINIMUM DEVICE LOCATIONS AND |
| | LEVELS PER FBC 11-4.28.1,.2 AND .3. |
| | BASE PLANS ARE REQUIRED TO MINIMUM DESIGN FIRE ALARM |
| | SYSTEM PER FS 633. |
| | |
| | 6) NOTE: NOTICE TO FS 553.80(2)(B) IS GIVEN WITH |
| | RESPECT TO REPEAT COMMENTS. THIS IS ONLY A NOTICE. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |