| Plan Review Notes For Permit 08080340 |
| Permit Number |
08080340 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-08 10:20:34 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. THE PRROJECTED SCOPE OF WORK SHALL NOT HINDER OR | | | INTEREFERE WITH ACCESS TO AND/OR EGRESS FROM OTHER | | | FLOORS OF THE BUILDING. | | | | | | 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 4. BASED UPON OCCUPANCY CLASSIFICATION, PLEASE PROVIDE | | | THE OCCUPANT LOAD FOR THE PROJECT SITE. | | | | | | 5. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE | | | TO EXITS. | | | | | | 6. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THE | | | NEW NINTH FLOOR PLAN. | | | | | | 7. SHOW THE LOCATION OF THE FIRE ALARM DEVICES FOR THE | | | NEW NINTH FLOOR PLAN. | | | | | | 8. SHOW THE LOCATION OF THE 2A:10BC FIRE | | | EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE. | | | | | | 9. SPECIFY THE INTERIOR WALL FINISH MATERIALS IN TERMS | | | OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|