| 2008-08-29 16:07:01 | |
| | |
| | |
| | |
| | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLANS NEED TO INDICATE THE MINIMUM CODES AS |
| | NOTED BELOW FOR DESIGN. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLANS NEED TO BE COMPLETED FOR LIGHTING |
| | CONTROL SYSTEM PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | STATING ON PLANS THAT THE SYSTEM SHALL BE LUTRON SOFT |
| | TOUCH OR EQUAL DOES NOT PROVIDE ENOUGH INFORMATION FOR |
| | REVIEW. PLEASE SHOW ALL DEVICES, LOCATIONS, OVER RIDES, |
| | OVER RIDE TIMES ETC |
| | |
| | 3) NOTE: PLEASE PROVIDE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2 |
| | PLEASE COMPLETE FIXTURE LEGEND ETC. AS THIS IS NOT |
| | COMPLETE AT THIS TIME THE LIGHTING PERFORMANCE LEVELS |
| | AS SHOWN CAN NOT BE CONFIRMED TO BE CODE COMPLIANT. |
| | |
| | 4) NOTE: PLEASE SEE THAT PANEL ON SECONDARY SIDE OF |
| | TRANSFORMER SHALL MEET 408.36, 240.21, 310.16, 240.4 |
| | |
| | 5) NOTE: PLEASE SEE FEEDERS ON THE SECONDARY SIDE OF |
| | TRANSFORMER SHALL MEET 240.21, 310.16, 240.4 |
| | |
| | 6) NOTE: PLEASE SEE 408.4, ALL NEW CIRCUITS SHALL BE |
| | SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. STATING |
| | *RECEPTACLES* OR *LIGHTING* IS NOT PERMITTED. |
| | |
| | 7) NOTE: PLEASE PROVIDE NOTES ON PLANS PER |
| | 13-413.1.ABC.2.1, .2.2 |
| | |
| | 8) NOTE: PLEASE COORDINATE PLANS. THE ELECTRICAL |
| | SERVICE EQUIPMENT SHOWN ON PLANS IS NOT THAT OF THE |
| | SAME EQUIPMENT SHOWN ON RISER AND PANEL SCHEDULES. |
| | 220,215,408,310,ETC |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION OF DOCUMENTS. |
| | FBC 106.3.5.1.2 FOR COMPLETED PLANS. |
| | |
| | 9) NOTE: PLEASE SHWO AND INDICATE ALL MINIMUM DEVICE |
| | LOCATIONS AND LEVELS PER FBC 11-4.28.1,.2 AND .3. |
| | BASE PLANS ARE REQUIRED TO MINIMUM DEISGN FIRE ALARM |
| | SYSTEM PER FS 633 |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |