| 2008-09-02 10:11:25 | BUILDING PLAN REVIEW |
| | PERMIT: 08080340 |
| | ADD: 1645 PALM BEACH LAKES # 900 |
| | CONT: LTI DEVELOPMENT |
| | TEL: (561)718-6243 |
| | |
| | SEPT. 02.08 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION919. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. PLANS SUBMITTED FOR PERMIT (FIRST TIME |
| | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| | 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| | 2004 EXISTING BUILDING CODE/ 2007 SUPPLEMENTS. |
| | B) LEVEL OF ALTERATION: 2004 EXISTING BUILDING CODE |
| | 301.5 A DESIGN PROFESSIONAL MUST ELECT ONE LEVEL OF |
| | ALTERATION PURSUANT TO SECTION 303,304 & 305. |
| | C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | D) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | . |
| | 3) SHEET 1.0A INDICATE A NEW BREAK ROOM BUT THERE IS NO |
| | INFORMATION ON THE BREAK ROOM CABINETS COUNTER AND |
| | SINK. PLEASE PROVIDE COMPLIANCE WITH: SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH |
| | THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW |
| | FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 |
| | |
| | 4) SHEET 1.0A INDICATES A NEW BREAK ROOM WITH NEW WASTE |
| | LINES BUT NO PLUMBING DETAILS NOR FIRE PROOFING DETAILS |
| | WHERE THE WASTE WILL PENETRATE THE FIRE RATED FLOOR |
| | ASSEMBLY. 712.4.1. |
| | |
| | 5) SHEET 2.0E THE RIGHT SET OF STAIRS IS MISSING THE |
| | EXIT LIGHT AT THE ENTRY OF THE VERTICAL EXIT. TABLE |
| | 1006. |
| | |
| | 6) PLANS DO NOT INDICATE THAT NO COMBUSTIBLE MATERIALS |
| | CAN BE USED IN THE CONSTRUCTION OF WALL FRAMING. TABLE |
| | 601, AND SECTION 603. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |