Plan Review Notes
Plan Review Notes For Permit 08080315
Permit Number 08080315
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-20 11:17:41PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-2 DETAIL 1, ELEVATIONS: PLEASE DELETE THE
 FOLLOWING "19" MAX CLEAR AREA UNDERNEATH SINK IS
 AVAILABLE UPON REMOVAL OF BASE CAB DOORS" FROM THIS
 DETAIL. PLEASE KNOW THAT THERE ARE NO EXCEPTIONS BEING
 INDICATED IN THE CODE AS INDICATED ON PLAN SHEET.
 PLEASE KNOW THAT THIS IS NOT COMPLIANT TO THE FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
  
 2. SHEET P-1 WATER ISOMETRIC: CLEARLY INDICATE THE
 FOLLOWING COMPLIANT WITH THE FBC-2004 PLUMBING CODE
 SECTIONS.
  
 A} POTABLE WATER SUPPLY TO THE ICE MAKER AND COFFEE
 MAKER. PER SECTION 601.1 SCOPE.
  
 B} SHUT OFF VALVES FOR THE ICE MAKER AND COFFEE MAKER.
 PER SECTION 602.2 (3) LOCATION OF SHUT OFF VALVES.
  
 C} THE REQUIRED WATER HAMMER ARRESTORS FOR THE POTABLE
 WATER SUPPLY TO THE REFRIGERATOR ICE MAKER AND COFFEE
 MAKER. PER SECTION 604.9 WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE QUICK CLOSING VALVES
 ARE UTILIZED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  