| Plan Review Notes For Permit 08080305 |
| Permit Number |
08080305 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-14 16:00:13 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:ALL | | | COMMENTS ARE FROM SHEET #4 OF 5. | | | | | | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN | | | IS NEW OR EXISTING. IF NEW INCLUDE AN AIC RATING, AND | | | LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER | | | ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE | | | WITH ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A | | | RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND | | | TYPE. | | | | | | 2} INDICATE THE SIZE AND OCP FOR THE DISCONNECT SHOWN. | | | NOTE: THE FEEDERS FOR THE 150 AMP PANEL ARE #10 (30 | | | AMP?). | | | | | | 3} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH | | | 250.66. INDICATE SIZE AND COMPLIANCE WITH 250.52. | | | | | | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220. | | | | | | 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE POOL | | | HEATER (TWO COPIES). | | | | | | 6} INDICATE COMPLIANCE WITH 680.26(C) EQUIPOTENTIAL | | | BONDING GRID BY DIAGRAM OR WITH A NOTE INDICATING HOW | | | IT WILL BE INSTALLED. SEE SENATE BILL 2836 APPROVED BY | | | THE GOVERNOR ON 6.19.07 FOR ALTERNATIVE METHOD. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|