 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:ALL
 COMMENTS ARE FROM SHEET #4 OF 5.
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE AN AIC RATING, AND
 LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER
 ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A
 RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND
 TYPE.
  
 2} INDICATE THE SIZE AND OCP FOR THE DISCONNECT SHOWN.
 NOTE: THE FEEDERS FOR THE 150 AMP PANEL ARE #10 (30
 AMP?).
  
 3} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. INDICATE SIZE AND COMPLIANCE WITH 250.52.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220.
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE POOL
 HEATER (TWO COPIES).
  
 6} INDICATE COMPLIANCE WITH 680.26(C) EQUIPOTENTIAL
 BONDING GRID BY DIAGRAM OR WITH A NOTE INDICATING HOW
 IT WILL BE INSTALLED. SEE SENATE BILL 2836 APPROVED BY
 THE GOVERNOR ON 6.19.07 FOR ALTERNATIVE METHOD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  