| Plan Review Notes For Permit 08080304 |
| Permit Number |
08080304 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-13 17:20:52 | 2004 FBC W/2007 REVISIONS | | | REROOF | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY WHICH ONE OF THE BASE SHEET FASTENING | | | OPTIONS AND DESIGN PRESSURE WILL BE INSTALLED. SEE PAGE | | | 26 WHICH WAS MISSING FROM THE NOA BUT IS PART OF THE | | | ASSEMBLY THAT GOES WITH PAGE 27 THAT WAS SUBMITTED. | | | R301.1 | | | | | | 2) SPECIFY HOW THE FASTENING AT THE PERIMETER AND | | | CORNER AREAS WILL BE ENHANCED AS CALCULATED IN | | | COMPLIANCE WITH RAS 117 TO MEET THE INCREASED UPLIFTS | | | IN THESE AREAS. SEE LIMITATION #7 ON PAGE 32 OF THE | | | NOA. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|