2008-08-27 16:48:22**DENIED**
  
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW AND NOT
 FOR PERMIT APPLICATION.
  
 2) NOTE: PLEASE SUBMIT ALL ELECTRICAL WHICH MAY BE PART
 OF THE SLAB/FOUNDATION. PLEASE SEE 250.50 AS THE
 MINIMUM IS REQUIRED FOR THE GROUNDING ELECTRODE SYSTEM.
 PLEASE SUBMIT THE GROUNDING ELECTRODE RISER FOR
 FOUNDATION WORK.
 PLEASE SUBMIT CONDUIT LAYOUT AND SIZES FOR ANY PROPOSED
 WORK WHICH MAY BE PART OF FOUNDATION.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  