| | ** DENIED 2ND REVIEW** |
| | |
| | ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF |
| | ADDRESSING. |
| | |
| | 1) NOTE: AS STATED ON PREVIOUS REVIEW. PLEASE DO NOT |
| | LEAVE OLD/VOIDED SHEETS IN SETS. PLEASE REMOVE |
| | COMPLETELY AND SET THE OLD SHEETS ASIDE INTO ONE SET. |
| | THE NEW SETS OF PLANS WITH REVISED SHEETS SHOULD ONLY |
| | CONTAIN NEW SHEETS WITH ANY SHEETS WHICH DID NOT NEED |
| | TO BE REVISED. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO |
| | LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2. PLANS |
| | ONLY SHOW A STANDARD SINGLE POLE SWITCH. |
| | |
| | 3) NOTE: NO LOAD CALCULATIONS WERE SUBMITTED FOR THE |
| | EXISTING PANEL HP WITH NEW LOADS BEING ADDED AS |
| | PREVIOUSLY NOTED. |
| | 220.87, 215.3,230.42 ETC. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |