Plan Review Notes
Plan Review Notes For Permit 08080248
Permit Number 08080248
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-05 15:49:10*****DENIED*****
  
  
 1. ON SHEET A00.30 GENERAL NOTE #2, REPLACE NFPA 2003
 WITH NFPA 1 - 2003 AS AN REFERENCE.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. THE CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT HINDER OR INTERFERE WITH ACCESS TO OR EGRESS FROM
 THE SUBJECT PROPERTYOR THE VICINITY THEREOF (INCLUDING
 STREETS, ROADS, FIRE LANES, ETC.) .
  
 4. SPECIFY THE NEW WALL AND CEILING INTERIOR FINISH IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  