| 2008-08-29 13:56:09 | |
| | |
| | |
| | |
| | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLANS NEED TO INDICATE THE MINIMUM CODES AS |
| | NOTED BELOW FOR DESIGN. |
| | 2004 FBC W/ 2007 REVISONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR LOADS ON |
| | EXISTING PANEL DP. PLEASE BE SURE ALL CONTINUOUS LOADS |
| | ARE SHOWN AT 125%. |
| | 220, 215.3, 230.42 ETC |
| | |
| | 3) NOTE: PLEASE INDICATE THE LIGHTING CONTROLS PER FBC |
| | 13-415.1.ABC.1.1,.1.2. |
| | |
| | 4) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR NEW FEEDERS |
| | PER 13-413.1ABC.1 |
| | |
| | 5) NOTE: PLEASE PROVIDE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | |
| | 6) NOTE: PLEASE SEE THAT PLANS, PANELS, RISER IS NOT |
| | COMPLETE AS THE RISER CONTAINS NOTES FOR A NEW PANEL |
| | *B* YET THE SUBMITTED PLANS DO NOT SHOW ANY NEW PANEL |
| | *B*. NO PANEL SCHEDULE, NO INFORMATION ON RISER ETC. |
| | PLEASE COMPLETE. |
| | 215.5, 408.4, 240.4, 310.16 |
| | FBC 106.3.5.1.2, 106.1.1 FOR CLARITY AND ADDITIONAL |
| | INFORMATION. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |