Plan Review Notes
Plan Review Notes For Permit 08080246
Permit Number 08080246
Review Stop P
Sequence Number 1
Notes
Date Text
2008-09-04 13:33:44****************PROVISO****************
 INFORMATION ONLY: SHEET A3 DETAIL 13, BATHROOM AND
 DRINKNG FOUNTAIN ELEV. PLEASE KNOW THAT THE FOLLOWING
 IS REQUIRED PER THE FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS FOR THE BATHROOM FIXTURES.
  
 **11-4.16 WATER CLOSETS
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
  
 **11-4.19 LAVATORIES AND MIRRORS
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON.
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
  
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM (SEE SHEET
 A2.0 DEMOLITION PLAN), DEAD ENDS SHALL BE PROHIBITED. A
 PLUMBING PERMIT IS REQUIRED AND AN INSPECTION IS
 REQUIRED OF PLUMBING DEMO WORK PRIOR TO COVERING DEMO
 WORK WITH FINNISH WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER