2008-08-12 10:37:20**ZONING FAILED **
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDRS.IF YOU HAVE ANY QUESTIONS REGARDING THE
 LANDSCAPE PLAN, PLEASE CONTACT ROBERT KUSSNER,
 LANDSCAPE PLANNER, AT 561-822-1435.
  
 3. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY?S ADDRESS AND LEGAL DESCRIPTION.
  
 INDICATE THE SETBACK DIMENSIONS FROM ANY EXTERIOR
 IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES.NOTE:
 PER SECTION 94-72, (SINGLE-FAMILY LOW DENSITY (SF7)
 RESIDENTIAL DISTRICT) OF THE ZLDRS: MINIMUM SETBACKS
 FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT