2008-08-18 13:22:25PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 1.4 THE EXISTING AND NEW PLAN VIEW DO NOT
 INDICATE THE REQUIRED AUTOMATIC CLOTHES WASHER
 CONNECTION. PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES FOR ANOCCUPANCY
 R-3 ONE AND TWO FAMILY DWELLING.
  
 2. SHEET 1.4 THE EXISTING AND NEW PLAN VIEW DO NOT
 INDICATE THE LOCATION OF THE REQUIRED WATER HEATER. PER
 FBC-2004 PLUMBING SECTION 607.1 WHERE REQUIRED.
  
 3. SHEET 2.4 CODES FOR REFERENCE IS INDICATING THE
 WRONG GOVERNING CODE AS 2006 REVISIONS. PLEASE DECLARE
 THE CORRECT GOVERNING CODE AS BEING FBC-2004 WITH 2007
 REVISIONS. PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTON OF CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  