| 2008-08-15 14:39:25 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET A-1, UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} PLEASE VERIFY THAT THE DESIGNER INTENDS TO REDUCE |
| | THE SERVICE FROM 200 AMPS TO 150 AMPS WHILE INCREASING |
| | THE SQUARE FOOTAGE OF THE RESIDENCE ?? |
| | |
| | 2} THERE ARE FOUR SMALL APPLIANCE CIRCUITS ON THE PANEL |
| | SCHEDULE, ONLY TWO (300 VA)IN THE LOAD CALCULATION. |
| | |
| | 3} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE, GROUNDING DETAILS, SEE 250.66 AND |
| | 250.52.NOTE FOOTER STEEL IS AVAILABLE. |
| | |
| | 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE ALARMS |
| | ON THE PLAN. |
| | |
| | 5} THE DISCONNECT LOCATION FOR THE A/C CONDENSER DOE |
| | NOT COMPLY WITH 110.26 SPACE REQUIREMENT. |
| | |
| | 6} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| | DEFICIENCIES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |