 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PLEASE VERIFY THAT THE DESIGNER INTENDS TO REDUCE
 THE SERVICE FROM 200 AMPS TO 150 AMPS WHILE INCREASING
 THE SQUARE FOOTAGE OF THE RESIDENCE ??
  
 2} THERE ARE FOUR SMALL APPLIANCE CIRCUITS ON THE PANEL
 SCHEDULE, ONLY TWO (300 VA)IN THE LOAD CALCULATION.
  
 3} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, SEE 250.66 AND
 250.52.NOTE FOOTER STEEL IS AVAILABLE.
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE ALARMS
 ON THE PLAN.
  
 5} THE DISCONNECT LOCATION FOR THE A/C CONDENSER DOE
 NOT COMPLY WITH 110.26 SPACE REQUIREMENT.
  
 6} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  