Plan Review Notes
Plan Review Notes For Permit 08080218
Permit Number 08080218
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-14 14:40:37RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
  
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT.SEC.
 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT
 PICK UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD. (561)233-5120)TO VERIFY IF
 IMPACT FEES ARE DUE.BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 4- PERMIT VALUATION WAS UPDATED TO $65,321 AS REQUIRED
 BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.OWES
 $1,171.18 FOR PERMIT VALUATION AND RADON FEES.
 ***NOTE: PERMIT FEE WAS NOT PAID AT TIME OF PERMIT
 APPLICATION. ALL FES NEED TO BEPAID AT TIME OF
 RE-SUBMITTAL. OTHERWISE REVIEWS WON'T BE PERFORMED.
  
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.2.2 OF FBC 2004.
 ***NOTE:PLEASE MAKE SURE CORRECT AND UPDATED FORM IS
 SUBMITTED TO AVOID ANY UNNECESSARY DELAYS.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES)AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ENTRY DOOR WITH SIDELITE ASSEMBLY AS SHOWN ON
 PLANS AND EXTERIOR ELEVATIONS. THERE WERE TWO
 DIFFERENT DOORPRODUCT APPROVALS SUBMITTED AND NONE OF
 THEM HAVE SIDELITE.NOA 02-1211.10 AND NOA
 07-0731.04.PROVIDE 2 COPIES OF PRODUCT APPROVAL FOR
 EACH DOOR MODEL.ONE FOR THE ENTRY DOOR AND OTHER FOR
 THE REAR DOOR.CLEARLY MARK WHICH DOOR IS THE ENTRY
 DOOR AND WHICH IS THE REAR DOOR.
 ***NOTE: NOA 02-1211.10 EXPIRED ON JULY. NEED TO
 PROVIDE CURRENT PRODUCT APPROVAL.
  
 B) SINGLE HUNG WINDOWS.COPIES OF DRAWING SUBMITTED
 ARE INCOMPLETE. THEY ARE MISSING THE TOP PORTION OF THE
 PAGE. PROVIDE COPIES WITH COMPLETE DRAWINGS.
  
 C) FLAT ROOF:
 (1) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING
 PERMITS. SEE ATTACHED COPY.
 (2) ON SELECTED ASSEMBLY, CLEARLY MARK SPECIFIC BASE
 SHEET FASTENING OPTION. SEE CITY POLICY.
 (3) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS.SEE GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA 03-0501.02 SUBMITTED.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
 ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED
 TO SUBMIT FULL REPORT. (THIS APPLIES TO CONNECTORS
 PRODUCT APPROVAL ONLY).
  
 E) WINDOW MULLIONS.AND, CLEARLY MARK SPECIFIC
 MULLION SIZE AND FASTENING TO VERIFY COMPLIANCE WITH
 THE CALCULATED DESIGN PRESSURES. SEC. R301 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3CITY AMENDMENTS TO FBC
 2004.
  
 8- SHEET 1.4:
 A) TYPICAL WALL SECTION (FLAT ROOF):
 (1) ROOF JOIST SIZE IS DIFFERENT THAN SIZE SHOWN ON
 ROOF FRAMING PLAN. REVISE.
 (2) R-30 INSULATION DOESN'T FIT ON 2X8 RAFTER.
 REVISE AS REQUIRED.
 (3) SPECIFYVENTILATION SIZE TO VERIFY COMPLIANCE
 WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
 (4) NUMBER OFREINFORCEMENT BARS ON FOOTING DON'T
 MATCH NUMBER SHOWN ON FOUNDATIONSCHEDULE. REVISE AS
 REQUIRED.
  
 B) TYPICAL WALL SECTION (PITCH ROOF):
 (1) ROOF PITCH OF 3 1/2:12REQUIRES 2 LAYERS OF
 UNDERLAYMENT.SPECIFYON DRAWINGS.SEC. R905.2.2 OF
 2004 FLORIDA RESIDENTIAL CODE.
 (2) PROVIDE CALCULATIONS AND LOCATION OF VENTILATION
 VENTS TO VERIFY COMPLIANCE WITH SEC. R806.
 SPECIFICATIONS CALL FOR 7"X24" VENTS @ 8'-0" O.C..
 ACCORDING TO THIS THERE IS ONLY ONE VENTSINCE THE
 ROOFSIDE IS LESS THAN 8'-0" AND THERE IS A GABLE END
 ON THE OTHER SIDE OF THE ROOF. IS ONE VENT ENOUGH TO
 VENTALL THE ROOF AREA?
 (3) REVISE NUMBER OF REBARS SHOWN ON FOOTING TO
 MATCH FOOTING SCHEDULE.
  
 C) WINDOWS SPECIFIED ON SCOPE OF WORK NOTE #1AND
 NOTE BELOW SCOPE OF WORK NOTES DON'T MATCHWINDOW
 SHOWN ON PRODUCT APPROVAL SUBMITTED. REVISE AS REQUIRED
 TO MATCH.
  
 D) CLARIFY BUCK NOTE:SPECIFY WHAT CODE SECTION
 REQUIRES ALL IMPACT RESISTANT WINDOWS AND DOORS TO HAVE
 2XBUCKS?AND, THEN WHYDOOR AND WINDOW ANCHORS
 DETAIL AT BOTTOM OF PAGE DON'T SPECIFY THE 2X BUCKS.
 REVISE AS REQUIRED.
  
 9- SHEET2.4:
 A) DOORS AND WINDOWS SPECIFIED ON THE EXTERIOR
 ELEVATIONS DON'T MATCH THOSE SHOWN ON THE PRODUCT
 APPROVALS PROVIDED. REVISE AS REQUIRED TO MATCH.
  
 B) AIRPORT ACOUSTICAL REQUIREMENTS:
 (1)NOTE #1:FURRING SIZE AND INSULATIONR-VALUE
 DON'T MATCH INFORMATION SHOWN ON TYPICAL WALL SECTIONS.
 (ALSO, COORDINATE THIS INFORMATION WITHENERGY
 CALCULATIONS TO AVOID DELAYS OR CONFLICTS.
 (2) COORDINATEINSULATION R-VALUE WITHREVISED
 INFORMATION OF ITEM # 8(A)(2) ABOVE.
 (3) PROVIDE INFORMATION SHOWING COMPLIANCE WITH NOTE
 #3.
  
 C) DESIGN PARAMETERS BOX:
 (1) UPDATE CODE SEC. ONE AND TWO FAMILYSINGLE
 FAMILY RESIDENCES ARE GOVERNED BY THE 2004 FLORIDA
 RESIDENTIAL CODE. SEE SEC. R301AND REVISE INFORMATION
 AS REQUIRED.CHAPTER 1609.6A-D DOESN'T APPLY. REVISE
 AS REQUIRED.
 (2) DESIGN LOADS DON'T MATCH DESIGN LOADS SHOWN ON
 STRUCTURAL NOTE #2. REVISE AS REQUIRED.
 (3) UPDATE THE CODE REFERENCES. SPECIFY2007
 REVISIONS, NOT 2006.
  
 D) UPDATE STRUCTURAL NOTE #12. SEE 2004 FLORIDA
 RESIDENTIAL CODE AND SPECIFY CORRECT CODE SECTION.
  
 E) WHERE IS DETAIL"A"SPECIFIED ON STRUCTURAL
 NOTE #13?
  
 F)STRUCTURAL NOTE #14:REVISE SIZE OF NAIL.NAIL
 NEEDS TO BE 1 3/4" EMBEDDED PER ASTM C1063.
 ALSO, CLARIFY WHAT'S "OR 1/2" EXT. PLYWOOD VENT SYSTEM
 REQUIRED"?
  
 10- SHEET 3.4:UPDATE MASONRY WALLS NOTES. SEE 2004
 FLORIDA RESIDENTIAL CODE AND UPDATENOTES WITH
 CORRESPONDING CODE SECTIONS.
  
 11- SHEET 4.4:
 A) COORDINATE ADDED DESIGN LOADS WITH DESIGN LOADS
 ON SHEET 2.4.
  
 B) COORDINATEROOF SHEATHING NAILING SPACING SHOWN
 ON PLYWOOD ROOF SHEATHINGNOTE CAND SPACING SHOWN ON
 COMPONENT AND CLADDING PRESSURES ZONES.
 ALSO, REVISENOTE C REGARDING THE ROOF ZONE 1 EXPOSURE
 ASSUMED FOR ENTIRE ROOF.THIS IS INCORRECT.ZONE 1 IS
 THE LESS STRICT ROOF ZONE.
  
 C) REVISE PLYWOOD ROOF SHEATHING NOTE D:NAIL SIZE
 NEEDS TO BE LONGER TO COMPLY WITH 1 3/4" MIN.
 EMBEDMENT.ASTM C1063.
  
 D) REVISE SIZE OF ROOF JOIST SPECIFIED ON DETAILS
 8/4.4 AND 9/4.4 TO MATCH ROOF FRAMING PLAN.
  
 E) REVISE TYPE OF NAIL SPECIFIED ON GENERAL ROOF
 NOTE #7 TO MATCH CORRECT INFORMATION GIVEN ON THE
 COMPONENTS AND CLADDING PRESSURES ZONES.
  
 12- PLEASE RETURN REVIEWED SET AFTERORIGINAL DRAWINGS
 ARE REVISED TO EXPEDITE THE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712