| Date |
Text |
| 2008-08-13 16:58:44 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P-1 SANITARY ISOMETRIC AND PLUMBING FLOOR |
| | PLAN: PLEASE CORRECT THE FOLLOWING PER THE FBC-2004 |
| | PLUMBING CODE SECTIONS. |
| | |
| | A} THE WASHING MACHINE MUST DRAIN DOWN STREAM OF THE |
| | NEW MATER BATH WET VET. ONLY FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. PER SECTION 909.1 |
| | WET VENT PERMITTED. |
| | |
| | B} CLEARLY INDICATE THE SIZE TO ALL FIXTURE TRAPS |
| | (WASHING MACHINE MINIMUM 2" AND LAVATORY MINIMUM 1-1/4" |
| | TRAPS ARE NOT SIZED). PER SECTION 701.1 SCOPE. |
| | |
| | C} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF |
| | THE BUILDING DRAIN AND BUILDING SEWER AS BEING A |
| | TWO-WAY CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN |
| | AND BUILDING SEWER JUNCTION. |
| | |
| | 2. SHEET P-1 PLUMBING FLOOR PLAN IS TO LIGHT AND HARD |
| | TO READ, PLEASE CORRECT. PER (W.P.B. AS AMENDED) |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. SHEET P-1 GAS ISOMETRIC: PLEASE KNOW THAT THE |
| | CORRECT SIZING TABLE IS 402.4(2) NOT 402.4(1) DUE TO |
| | FLORIDA PUBLIC UTILITIES PROVIDING A 12" WC WITH A .5" |
| | PRESSURE DROP. PER FBC-2004 FUEL GAS TABLE 402.4(2). |
| | |
| | 4. PLEASE KNOW THAT ENERGY CALCULATIONS FOR THE NEW |
| | TANKLESS WATER HEATER AND HOT WATER PIPE INSULATION ARE |
| | REQUIRED. PER FBC-2004 CHAPTER 13 SECTION 13-612.1.C.1 |
| | ADDITIONS, TABLE 13-612.1.ABC.3.2 MINIMUM PERFORMANCE |
| | STANDARDS WATER HEATING EQUIPMENT, AND TABLE |
| | 611.1.ABC.1 MINIMUM PIPE INSULATION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |