| 2008-08-29 11:14:48 | ****CORRECTIONS**** |
| | ****PLANS ROUTED TO BE ISSUED*** |
| | ****INFORMATIONAL FOR CONTRACTOR TO ASSIST IN |
| | COMPLETING INSTALLATION SCHEDULE PROPERLY. PLANS ROUTED |
| | TO BE ISSUED*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| | OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. ADDRESSED. |
| | |
| | 2. FOR THE ACCORDIONS, PLEASE COMPLETE THE INSTALLATION |
| | SCHEDULE. THE ANCHOR SPACING WAS NOT COMPLETED ON THE |
| | SECOND PAGE. |
| | |
| | 3. PLEASE REVISE SHUTTER CONNECTION MOUNTING TYPE TO |
| | CORRELATE WITH THE ANCHOR SCHEDULE. FOR INSTANCE, C1 |
| | THROUGH C5. YOU'VE SPECIFIED WALL, BUT CIRCLED TWO |
| | DIFFERENT ANCHOR TYPES AND TWO DIFFERENT ANCHORS ON |
| | SHEET 3, CLEAR PANEL PRODUCT APPROVAL. CIRCLING ITEMS |
| | ON THE PRODUCT APPROVAL CAN BE HELPFUL FOR |
| | REVIEW/INSPECTIONS BUT MUST CORRELATE WITH THE JOB AND |
| | THE INSTALLATION SCHEDULE. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. ALL STILL SAY "WALL"; PLEASE |
| | REVISE. FOR EXAMPLE, STORM PANELS 2250 SPECIFY 7" |
| | SPACING, SUBSTRATE IS NOT COMPLETED BUT "MASONRY" |
| | CHECKED AT THE TOP. SHEET 5 OF THE PRODUCT APPROVAL, |
| | CANNOT DETERMINE WHICH MOUNTING TYPE YOU ARE USING BUT |
| | EACH HAS A DIFFERENT REQUIREMENT AND 7" IS NOT |
| | COMPLIANT FOR ANY OF THEM. |
| | |
| | CLEAR PANELS, STATE "WALL", NO SUBSTRATE INFORMATION |
| | PROVIDED. THE PRODUCT APPROVAL HAS C1 AND C4 CIRCLED. |
| | 13" APPEARS COMPLIANT IF THE SUBSTRATE IS CONCRETE, BUT |
| | NOT FOR MASONRY. PLEASE SPECIFY SUBSTRATE AND CLARIFY |
| | CONNECTION TYPE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |