| 2008-08-21 14:18:38 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.FOR THE CLEAR PANELS, IT APPEARS THAT YOU HAVE USED |
| | THE ANCHOR SPACING FOR A CONCRETE SUBSTRATE.THIS |
| | PANEL IS BEING INSTALLED HORIZONTALLY; PROVIDE EVIDENCE |
| | THAT THERE IS FORMED AND POURED CONCRETE ON EACH SIDE |
| | OF THESE OPENINGS.FILLED CELLS (MASONRY SUBSTRATE) IS |
| | TYPICALLY INSTALLED AT THESE LOCATIONS. |
| | |
| | 2.FOR THE ACCORDIONS, PLEASE COMPLETE THE |
| | INSTALLATION SCHEDULE.THE ANCHOR SPACING WAS NOT |
| | COMPLETED ON THE SECOND PAGE. |
| | |
| | 3.PLEASE REVISE SHUTTER CONNECTION MOUNTING TYPE TO |
| | CORRELATE WITH THE ANCHOR SCHEDULE.FOR INSTANCE, C1 |
| | THROUGH C5.YOU'VE SPECIFIED WALL, BUT CIRCLED TWO |
| | DIFFERENT ANCHOR TYPES AND TWO DIFFERENT ANCHORS ON |
| | SHEET 3, CLEAR PANEL PRODUCT APPROVAL.CIRCLING ITEMS |
| | ON THE PRODUCT APPROVAL CAN BE HELPFUL FOR |
| | REVIEW/INSPECTIONS BUT MUST CORRELATE WITH THE JOB AND |
| | THE INSTALLATION SCHEDULE. |