| Date |
Text |
| 2008-12-23 11:21:27 | ** DENIED** |
| | |
| | 1) NOTE: DETERMINATION OF LIGHTING POWER DENSITY |
| | COMPLIANCE CAN NOT BE MADE THE FIXTURE LEGEND IS STILL |
| | NOT COMPLETE. FOR EXAMPLE: PLEASE SEE THE TRACK |
| | LIGHTING WHICH ONLY INDICATES THE TYPE OF TRACK. THE |
| | FIXTURE MUST BE SHOWN AS THE WATTAGE PER |
| | 13-415.2.ABC.1.1 IS BASED ON THE VA RATING OF EACH |
| | FIXTURE OR 30 VA PER LINEAR FOOT OF TRACK, **WHICH EVER |
| | IS GREATER*. IF THE TRACK LIGHTING FIXTURES WERE FOR |
| | EXAMPLE 75WATT FIXTURES WITH THE NUMBER OF FIXTURES |
| | SHOWN THE TOTAL WATTAGE WOULD BE 2550. THIS WOULD BE |
| | FAR GREATER THAN THE 1560 WATTS FIGURED AT 30VA PER FT. |
| | THE ENERGY CODE IS BASED ON THE WATTAGE WHICH IS |
| | GREATER, NOT JUST A MINIMUM. EVEN IF THE FIXTURES WERE |
| | ONLY RATED AT 50WATTS THIS WOULD STILL BE MORE THAN THE |
| | 1560 SHOWN IN CALCULATIONS. |
| | |
| | ** BASED ON EACH OF THESE TWO EXAMPLES OF 75W OR 50W |
| | FIXTURES, THE ALLOWANCES AS SHOWN WOULD BE OVER BASED |
| | ON CALCULATIONS SHOWN FOR MAXIMUM ALLOWANCES. |
| | AS STATED IN THE TWO PREVIOUS REVIEWS ALONG WITH THIS |
| | REVIEW IF THERE ARE ANY QUESTIONS PLEASE CALL. LIGHTING |
| | ALLOWANCES FOR SPACE BY SPACE NEED TO BE SHOWN FOR |
| | SPACE BY SPACE. SOME AREAS MAY BE OVER AS LONG AS SOME |
| | OTHER AREAS ARE LESS AND THE TOTAL ALLOWANCE IS NOT |
| | EXCEEDED. |
| | |
| | |
| | 2) NOTE: THE SPECIAL INSPECTOR AGREEMENT CONTAINS A |
| | RAISED SEAL OVER PHOTO-COPIED SIGNATURES. IN FACT ALL |
| | SHEETS ARE PHOTO-COPIES INCLUDING THE SIGNATURES AND |
| | STAMPS FROM ALL PARTIES. NOTARY, ENGINEER, INSPECTOR |
| | ETC. PLEASE SEE FS 553.79, 471.025, 117, FAC |
| | 61G15-23.002. ALL MUST ORIGINAL. |
| | ONLY ONE COPY WAS GIVEN TO CONTRACTOR TO OBTAIN ALL NEW |
| | ORIGINALS. |
| | THE ENGINEER OF RECORD RAISED SEAL FOR MR. OSVALDO |
| | AREVALO IS PLACED OVER PHOTO-COPIED LETTERS AND |
| | SIGNATURES. |
| | ** THESE TWO COPIES WILL BE RETAINED BY THIS OFFICE. |
| | DOCUMENTS ALSO SHOWN TO INTERIM ASSISTANT BUILDING |
| | OFFICIAL RONALD REGUEIRO. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |