Plan Review Notes
Plan Review Notes For Permit 08080195
Permit Number 08080195
Review Stop E
Sequence Number 3
Notes
Date Text
2008-12-23 11:21:27** DENIED**
  
 1) NOTE: DETERMINATION OF LIGHTING POWER DENSITY
 COMPLIANCE CAN NOT BE MADE THE FIXTURE LEGEND IS STILL
 NOT COMPLETE. FOR EXAMPLE: PLEASE SEE THE TRACK
 LIGHTING WHICH ONLY INDICATES THE TYPE OF TRACK. THE
 FIXTURE MUST BE SHOWN AS THE WATTAGE PER
 13-415.2.ABC.1.1 IS BASED ON THE VA RATING OF EACH
 FIXTURE OR 30 VA PER LINEAR FOOT OF TRACK, **WHICH EVER
 IS GREATER*. IF THE TRACK LIGHTING FIXTURES WERE FOR
 EXAMPLE 75WATT FIXTURES WITH THE NUMBER OF FIXTURES
 SHOWN THE TOTAL WATTAGE WOULD BE 2550. THIS WOULD BE
 FAR GREATER THAN THE 1560 WATTS FIGURED AT 30VA PER FT.
 THE ENERGY CODE IS BASED ON THE WATTAGE WHICH IS
 GREATER, NOT JUST A MINIMUM. EVEN IF THE FIXTURES WERE
 ONLY RATED AT 50WATTS THIS WOULD STILL BE MORE THAN THE
 1560 SHOWN IN CALCULATIONS.
  
 ** BASED ON EACH OF THESE TWO EXAMPLES OF 75W OR 50W
 FIXTURES, THE ALLOWANCES AS SHOWN WOULD BE OVER BASED
 ON CALCULATIONS SHOWN FOR MAXIMUM ALLOWANCES.
 AS STATED IN THE TWO PREVIOUS REVIEWS ALONG WITH THIS
 REVIEW IF THERE ARE ANY QUESTIONS PLEASE CALL. LIGHTING
 ALLOWANCES FOR SPACE BY SPACE NEED TO BE SHOWN FOR
 SPACE BY SPACE. SOME AREAS MAY BE OVER AS LONG AS SOME
 OTHER AREAS ARE LESS AND THE TOTAL ALLOWANCE IS NOT
 EXCEEDED.
  
  
 2) NOTE: THE SPECIAL INSPECTOR AGREEMENT CONTAINS A
 RAISED SEAL OVER PHOTO-COPIED SIGNATURES. IN FACT ALL
 SHEETS ARE PHOTO-COPIES INCLUDING THE SIGNATURES AND
 STAMPS FROM ALL PARTIES. NOTARY, ENGINEER, INSPECTOR
 ETC. PLEASE SEE FS 553.79, 471.025, 117, FAC
 61G15-23.002. ALL MUST ORIGINAL.
 ONLY ONE COPY WAS GIVEN TO CONTRACTOR TO OBTAIN ALL NEW
 ORIGINALS.
 THE ENGINEER OF RECORD RAISED SEAL FOR MR. OSVALDO
 AREVALO IS PLACED OVER PHOTO-COPIED LETTERS AND
 SIGNATURES.
 ** THESE TWO COPIES WILL BE RETAINED BY THIS OFFICE.
 DOCUMENTS ALSO SHOWN TO INTERIM ASSISTANT BUILDING
 OFFICIAL RONALD REGUEIRO.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  