2008-11-15 13:42:22REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK: IT IS NOT CLEAR HOW TOTAL SEATS WILL PREDICT
 MAXIMUM OCCUPANCY, INCLUDING EMPLOYEES AND THOSE
 WAITING TO BE SEATED, BUT WILL DEFER TO THE JUDGEMENT
 OF THE DESIGN PROFESSIONAL.
  
 3. **PREVIOUS REVIEW COMMENT** PAGE M1.0: NOTE #1,
 WHICH REFERENCED 13-409.1.ABC.3.3 FOR SHUTOFF DAMPER
 CONTROLS, CALLS FOR MOTORIZED DAMPER ON THE OA INTAKE
 FOR AHU #1 WITH NO PROVISIONS FOR AHU #2 OR AHU #3.
 EVEN THOUGH THEY SHOW LESS THAN 300 CFM, A BACK DRAFT
 DAMPER, AT A MINIMUM, IS REQUIRED TO MEET THE
 REQUIREMENTS OF THIS CODE SECTION.
 **NOT ADEQUATELY ADDRESSED** PAGE M1.0 SHOWS THE
 ADDITION OF MANUAL VOLUME DAMPERS IN RESPONSE TO THIS
 COMMENT. AS STATED IN THE PREVIOUS REVIEW COMMENT, A
 BACKDRAFT DAMPER IS REQUIRED IN O.A. INTAKES IN LIEU OF
 THE MOTORIZED DAMPERS PER THE REFERENCED SECTION. THE
 MANUAL VOLUME DAMPERS SATISFY THE REQUIREMENTS OF
 13-409.1.ABC.1.1 BUT DO NOT SATISFY THE REQUIREMENTS OF
 13-409.1.ABC.3.3.
  
  
 4. **PREVIOUS REVIEW COMMENT** PAGE M2.0: DIFFUSER AND
 FLEXIBLE DUCT DETAILS ARE NOT CODE COMPLIANT. THE
 MINIMUM WIDTH OF HANGERS AND SUPPORTS FOR FLEXIBLE
 DUCTS SHALL BE 1.5 INCHES AND THE MAXIMUM SAG BETWEEN
 SUPPORTS SHALL BE 1/2 INCH PER FOOT IN ACCORDANCE WITH
 FBCM 603.5.6.6. ADJUST DETAILS TO SHOW COMPLIANCE WITH
 THIS SECTION.
 **NOT ADEQUATELY ADDRESSED** DETAIL NOW ALLOWS FOR A
 MAXIMUM OF 1.5 INCES OF SAG PER FOOT OF LENGTH RATHER
 THAN THE 0.5 INCHES PER FOOT OF LENGTH AS STATED IN
 PREVIOUS REVIEW COMMENT AND AS REQUIRED BY FBCM
 603.5.6.6(4).
  
 NOTE: METHOD C CALCS OK FOR MECHANICAL. SEE ELECTRICAL
 REVIEW COMMENTS.
  
 NOTE: NO INFORMATION WAS PROVIDED ON THESE PLANS
 REGARDING KITCHEN HOOD/EXHAUST AND WALK-IN COOLER
 SYSTEMS. SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 THESE SYSTEMS.
  