| 2008-11-15 13:42:22 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. OK |
| | |
| | 2. OK: IT IS NOT CLEAR HOW TOTAL SEATS WILL PREDICT |
| | MAXIMUM OCCUPANCY, INCLUDING EMPLOYEES AND THOSE |
| | WAITING TO BE SEATED, BUT WILL DEFER TO THE JUDGEMENT |
| | OF THE DESIGN PROFESSIONAL. |
| | |
| | 3. **PREVIOUS REVIEW COMMENT** PAGE M1.0: NOTE #1, |
| | WHICH REFERENCED 13-409.1.ABC.3.3 FOR SHUTOFF DAMPER |
| | CONTROLS, CALLS FOR MOTORIZED DAMPER ON THE OA INTAKE |
| | FOR AHU #1 WITH NO PROVISIONS FOR AHU #2 OR AHU #3. |
| | EVEN THOUGH THEY SHOW LESS THAN 300 CFM, A BACK DRAFT |
| | DAMPER, AT A MINIMUM, IS REQUIRED TO MEET THE |
| | REQUIREMENTS OF THIS CODE SECTION. |
| | **NOT ADEQUATELY ADDRESSED** PAGE M1.0 SHOWS THE |
| | ADDITION OF MANUAL VOLUME DAMPERS IN RESPONSE TO THIS |
| | COMMENT. AS STATED IN THE PREVIOUS REVIEW COMMENT, A |
| | BACKDRAFT DAMPER IS REQUIRED IN O.A. INTAKES IN LIEU OF |
| | THE MOTORIZED DAMPERS PER THE REFERENCED SECTION. THE |
| | MANUAL VOLUME DAMPERS SATISFY THE REQUIREMENTS OF |
| | 13-409.1.ABC.1.1 BUT DO NOT SATISFY THE REQUIREMENTS OF |
| | 13-409.1.ABC.3.3. |
| | |
| | |
| | 4. **PREVIOUS REVIEW COMMENT** PAGE M2.0: DIFFUSER AND |
| | FLEXIBLE DUCT DETAILS ARE NOT CODE COMPLIANT. THE |
| | MINIMUM WIDTH OF HANGERS AND SUPPORTS FOR FLEXIBLE |
| | DUCTS SHALL BE 1.5 INCHES AND THE MAXIMUM SAG BETWEEN |
| | SUPPORTS SHALL BE 1/2 INCH PER FOOT IN ACCORDANCE WITH |
| | FBCM 603.5.6.6. ADJUST DETAILS TO SHOW COMPLIANCE WITH |
| | THIS SECTION. |
| | **NOT ADEQUATELY ADDRESSED** DETAIL NOW ALLOWS FOR A |
| | MAXIMUM OF 1.5 INCES OF SAG PER FOOT OF LENGTH RATHER |
| | THAN THE 0.5 INCHES PER FOOT OF LENGTH AS STATED IN |
| | PREVIOUS REVIEW COMMENT AND AS REQUIRED BY FBCM |
| | 603.5.6.6(4). |
| | |
| | NOTE: METHOD C CALCS OK FOR MECHANICAL. SEE ELECTRICAL |
| | REVIEW COMMENTS. |
| | |
| | NOTE: NO INFORMATION WAS PROVIDED ON THESE PLANS |
| | REGARDING KITCHEN HOOD/EXHAUST AND WALK-IN COOLER |
| | SYSTEMS. SEPARATE PERMITS AND PLANS ARE REQUIRED FOR |
| | THESE SYSTEMS. |
| | |