| Date |
Text |
| 2008-11-03 08:53:38 | |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | THE SUBMITTED FORM *C* AS SHOWN MAY NOT BE USED AS IT |
| | IS SHOWING SPACE BY SPACE ALLOWANCES. TABLE *C* |
| | 13-415.2.C IS FOR BUILDING AREA TYPE. HOWEVER THE |
| | SUBMITTED FORM CLEARLY INDICATES TWO SEPARATE SPACES. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE |
| | FBC AS IT CLEARLY STATES YOU MAY NOT MIX |
| | METHODS/TABLE/ALLOWANCES. |
| | THE PLANS INDICATE THE SAME ALLOWANCE ALTHOUGH NOT |
| | INDICATING A METHOD OF CALCULATION. IN EITHER CASE THE |
| | ALLOWANCES AS SHOWN ARE NOT PERMITTED AND THE METHOD IS |
| | INCORRECT. |
| | THE DINING AREA AS SHOWN ON FORM INDICATES A 2.1 |
| | ALLOWANCE HOWEVER NO DINING AREAS AS SHOWN IN TABLE *C* |
| | IN THE CODE PERMITS THAT HIGH OF A LIGHTING LEVEL. IN |
| | FACT FAMILY DINING IN TABLE C WHICH IS THE HIGHEST IS |
| | 1.6. |
| | THE FOLLOWING IS A LINE FROM THIS SECTION OF THE CODE. |
| | 13-415.2.ABC.1. |
| | |
| | ** TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE |
| | AMONG PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT |
| | METHOD OF CALCULATION HAS BEEN USED ARE NOT PERMITTED. |
| | |
| | ** PLEASE SUBMIT AND SHOW COMPLIANCE WITH THE SECTIONS |
| | ABOVE AND IF THERE ARE QUESTIONS PLEASE CALL. ALLOWANCE |
| | AS NOTED ON FORM *C* IS OVER. |
| | |
| | PLEASE BE SURE TO SEE TRACK LIGHTING ALLOWANCES IN |
| | SECTIONS ABOVE. |
| | |
| | |
| | 2) NOTE: PLEASE INDICATE MORE INFORMATION FOR THE |
| | LIGHTING CONTROL SYSTEM PROPOSED. |
| | THE PLANS DO NOT INDICATE IF THERE ARE PILOT LIGHTS AS |
| | REQUIRED. SECTION 13-415.1.ABC.1.1,.1.2 REQUIRES THE |
| | OVER RIDE FOR NO MORE THAN 4HRS. THESE SAME SECTIONS |
| | REQUIRES THE OCCUPANT TO VISUALLY SEE ALL LIGHTING |
| | WHICH IS BEING CONTROLLED/OVER RIDDEN. IF THE OCCUPANT |
| | CAN NOT SEE *ALL* LIGHTS THEN THE EXCEPTION IS THAT THE |
| | LIGHTING CONTROLS REQUIRES PILOT/INDICATOR LIGHTS WHICH |
| | ARE REQUIRED TO BE LABELED. IF THE DEVICES AS NOTED |
| | CONTAIN THESE INDICATOR/PILOT LIGHTS THEN PLEASE |
| | IDENTIFY. |
| | |
| | 3) NOTE: PREVIOUS NOTE REQUESTED TO SHOW HOW THE TRACK |
| | LIGHTING LOADS PER 220.43 ARE FIGURED AND TO PLEASE |
| | SHOW. COULD NOT LOCATE ANY CHANGE TO THIS. |
| | |
| | 4) NOTE: IF BOTH SUITES WHICH ARE SHOWN AS 116 AND 120 |
| | ARE GOING TO HAVE TWO MAINS FEEDING WHAT IS NOW GOING |
| | TO BE ONE SUITE THAN THIS NEW SINGLE TENANT NEEDS TO |
| | HAVE SIGNAGE INDICATING THIS. AS THE APPLIED ADDRESS |
| | LOCATION AS SHOWN ON THE TITLE BLOCKS ARE SUITE #116 |
| | THAN THE MAINS FOR TENANT BOTH NEED TO BE LABELED SUITE |
| | #116 MAIN ONE OF TWO AND 2 OF TWO. RISER SHOWS TWO |
| | SEPARATE SUITES. IF THE FIRE DEPARTMENT OR ANY OTHER |
| | PERSONNEL NEEDED TO TURN POWER OFF IN ANY EVENT THESE |
| | WOULD NOT BE LABELED CORRECTLY. |
| | 230.2E, 225.37. (THESE ARE FEEDERS) THE CODE SECTIONS |
| | GIVEN ARE FOR SERVICE ENTRANCE AND FEEDERS. THE INTENT |
| | OF THE CODE SECTIONS ARE THE SAME AS ALL EQUIPMENT IS |
| | REQUIRED TO BE CORRECTLY LABELED. |
| | |
| | 5) NOTE: PLEASE INDICATE THE HEIGHTS OF DEVICE FOR |
| | HORN/STROBES AND ANY PULL STATIONS PER 11-4.28.1,.2 AND |
| | .3. |
| | THE MINIMUM CANDELA LEVELS ARE SHOWN WHICH ARE OK. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |