Plan Review Notes
Plan Review Notes For Permit 08080195
Permit Number 08080195
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-14 11:33:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE CITY WPB
  
 1. ALL SHEETS REQUIRE THE "CITY PLACE" APPROVAL STAMP
 PRIOR TO REVIEW BY CITY WPB.
  
 2. ALL SHTS WITH THE ARCHITECT'S TITLE BLOCK. THE
 ADDRESS ON THE TITLE BLOCK, 370 CAMINO GARDENS BLVD,
 DOES NOT REFLECT THE ADDRESS OF RECORD ON THE STATE OF
 FLORIDA, DBPR WEBSITE. PLEASE UPDATE EITHER THE TITLE
 BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING TO
 CITY WPB. FAC 61G1-16.004(1) & FS 481.2055.
  
 3. SHT A-1.0 CODES TO INDICATE ALL UPDATES UP TO 2007.
 SECTION 106.1.1.
  
 4. ALL ARCHITECTURAL SHEETS. A SIGNATURE IS REQUIRED ON
 THE DATED SEAL OF EACH SHEET. IT APPEARS THAT INITIALS
 HAVE BEEN USED. IF THIS IS INDEED THE LEGAL SIGNATURE,
 THEN A SIGNED, SEALED, NOTORIZED LETTER IS REQUIRED FOR
 OUR FILES INDICATING THE LEGAL SIGNATURE OF THE
 ARCHITECT, CRAIG MOSSEY. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055. PLEASE SUBMIT
 VERIFICATION LETTER. ^^^^^^^^(DELETE COMMENT NEXT
 REVIEW)^^^^^^^
  
 5. SHTS A-2.4 DETAIL #2 AND A-5.0 FINISH SCHEDULE.
 ROOMS 106 & 106 WALLS WITH IN 2 FEET OF THE WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE. EPOXY PAINT DOES NOT COMPLY WITH THE "HARD"
 REQUIREMENT. SECTION 1210.2. PLEASE INDICATE METHOD OF
 COMPLIANCE.
  
 6. SHT P1.0 SANITARY PLAN/ISOMETRIC. THE DISHWASHER
 SHALL DISCHARGE INTO THE SANITARY SYSTEM PER ARTICLE
 III SECTION 90-124(7)(B). PLEASE CHANGE FLOOR PLAN AND
 ISOMETRIC.
  
 7. SHT P1.0 SANITARY PLAN/ISOMETRIC. THE DISCHARGE FROM
 THE AIR PURIFICATION UNIT SHALL BE THRU AN INDIRECT
 WASTE RECEPTOR. SECTION 802.1.5. A FLOOR SINK OR HUB
 DRAIN IS REQUIRED FOR INDIRECT WASTE RECEPTOR. SECTIONS
 802.3 & 802.3.2.
  
 8. SHT P2.0 WATER PLAN/ISOMETRIC. A WATER HAMMER
 ARRESTOR IS REQUIRED ON THE WATER SUPPLY FOR THE
 DISHWASHER. SECTION 604.9. PLEASE SHOW ON THE
 ISOMETRIC.
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 10. SHT P3.0 FLOOR SINK DETAIL. THE AIR GAP SHALL BE
 PER SECTION 802.2.1, MINIMUM TWICE THE EFFECTIVE
 OPENING OF THE INDIRECT WASTE PIPE. PLEASE INDICATE ON
 DETAIL.
  
 11. SHT P3.0 ELECTRIC WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION 607.3.2. PLEASE
 INDICATE METHOD.
  
 12. SHT P3.0 GREASE INTERCEPTOR DETAIL NOTES INDICATES
 THE INLET PIPING SHALL EXTEND 24" BELOW THE WATER
 LEVEL, BUT THE DETAIL DOES NOT SHOW THIS. PER SECTION
 1003.5.3 THE INLET PIPING SHALL CONNECT TO A TEE WHICH
 SHALL EXTEND 24" BELOW THE WATER LEVEL. PLEASE HAVE
 DETAIL REFLECT REQUIREMENT. (CITY WPB APPROVED
 DETAIL).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved